Trane PKGP-PRC003-EN Performance, Data10 Ton, Table PD-36-10 Ton, Heating Capacities Net, WSC120A

Models: PKGP-PRC003-EN

1 56
Download 56 pages 28.86 Kb
Page 34
Image 34
Table PD-36— 10 Ton

Performance

Data(10 Ton)

Table PD-36— 10 Ton

Heating Capacities (Net)

WSC120A

 

At 4000 CFM Downflow Configuration

 

 

 

 

 

 

 

 

 

Outdoor

InagratedHeatingCapacity(Btuh/1000)

 

 

 

 

Total Power in Kilowatts at

 

 

Temp.

at Indicated Indoor Dry Bulb Temp.1

 

 

 

 

Indicated Indoor Dry Bulb Temp.

 

 

F.

60

70

75

80

 

60

70

75

80

 

8

39.6

39.4

39.4

39.5

 

7.15

7.76

8.11

8.49

 

-3

43.3

43.0

43.0

43.0

 

7.22

7.83

8.18

8.56

 

2

47.3

47.0

46.9

46.9

 

7.30

7.91

8.26

8.64

 

7

51.7

51.3

51.2

51.1

 

7.39

8.00

8.35

8.72

 

12

56.4

55.8

55.7

55.5

 

7.48

8.09

8.44

8.82

 

17

61.3

60.7

60.4

60.3

 

7.56

8.17

8.53

8.91

 

22

66.6

65.8

65.5

65.2

 

7.65

8.27

8.62

9.01

 

27

72.2

71.3

70.9

70.5

 

7.74

8.36

8.72

9.11

 

32

78.1

77.0

76.5

76.1

 

7.83

8.46

8.82

9.21

 

37

83.1

82.9

82.3

81.8

 

7.89

8.56

8.93

9.32

 

42

90.5

89.0

88.3

87.7

 

8.02

8.67

9.04

9.44

 

47

111.7

109.8

108.9

108.0

 

8.93

9.68

10.11

10.57

52

119.8

117.6

116.5

115.5

 

9.05

9.82

10.25

10.72

57

128.1

125.6

124.4

123.3

 

9.18

9.96

10.40

10.88

62

136.7

133.8

132.5

131.2

 

9.32

10.11

10.56

11.05

 

67

145.3

142.1

141.0

139.5

 

9.46

10.27

10.75

11.24

 

72

155.2

151.6

149.9

148.3

 

9.66

10.48

10.95

11.45

 

For other airflow conditions, see heating capacity correction factor (Table PD-39).

Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.

Note:

1.Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

Table PD-37— 10 Ton

Heating Capacities (Net)

WSC120A

 

At 4000 CFM Horizontal Configuration

Outdoor

IntegratedHeatingCapacity(Btuh/1000)

 

 

 

 

Total Power in Kilowatts at

 

 

Temp.

at Indicated Indoor Dry Bulb Temp.1

 

 

 

 

Indicated Indoor Dry Bulb Temp.

 

 

F.

60

70

75

80

 

60

70

75

80

 

-8

40.0

39.7

39.7

39.8

 

7.24

7.85

8.20

8.58

 

-3

43.6

43.3

43.3

43.3

 

7.32

7.93

8.27

8.65

 

2

47.7

47.3

47.2

47.2

 

7.40

8.00

8.35

8.73

 

7

52.1

51.6

51.5

51.4

 

7.49

8.09

8.44

8.81

 

12

56.7

56.2

56.0

55.8

 

7.57

8.18

8.53

8.90

 

17

61.7

61.0

60.8

60.6

 

7.66

8.26

8.62

9.00

 

22

66.9

66.1

65.8

65.5

 

7.74

8.36

8.71

9.09

 

27

72.5

71.6

71.2

70.8

 

7.83

8.45

8.81

9.19

 

32

78.5

77.3

76.8

76.4

 

7.92

8.55

8.91

9.30

 

37

83.4

83.2

82.6

82.1

 

7.98

8.65

9.01

9.41

 

42

90.8

89.3

88.6

88.0

 

8.11

8.75

9.12

9.52

 

47

112.0

110.1

109.2

108.3

 

9.01

9.76

10.19

10.65

52

120.1

117.8

116.8

115.8

 

9.14

9.90

10.33

10.80

57

128.4

125.9

124.6

123.5

 

9.27

10.04

10.48

10.96

62

137.0

134.1

132.7

131.5

 

9.40

10.19

10.64

11.12

 

67

145.6

142.3

141.2

139.8

 

9.55

10.35

10.82

11.31

 

72

155.4

151.8

150.2

148.5

 

9.74

10.56

11.03

11.52

 

For other airflow conditions, see heating capacity correction factor (Table PD-39).

Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.

Note:

1.Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

34

PKGP-PRC003-EN

Page 34
Image 34
Trane PKGP-PRC003-EN Performance, Data10 Ton, Table PD-36-10 Ton, Heating Capacities Net, WSC120A, Table PD-37-10 Ton

FAQ

What are the integrated heating capacities for the WSC120A model at 4000 CFM downflow configuration?

The integrated heating capacities range from 39,400 Btuh at 70°F to 155,200 Btuh at 72°F.

How does the demand defrost cycle affect heating capacities and power output?

Integrated heating capacities and power include the effects of defrost in the frost region. Heating capacities and power kw are at 70% OD relative humidity and demand defrost cycle.

What is the net heating capacity and power input at 4000 CFM horizontal configuration?

The net heating capacity ranges from 39,700 Btuh at -8°F to 155,400 Btuh at 72°F, with a corresponding power input of 7.24 kW to 9.74 kW.