Trane PKGP-PRC003-EN manual Performance, Data7½Ton, At 3000 CFM, Downflow Configuration

Models: PKGP-PRC003-EN

1 56
Download 56 pages 28.86 Kb
Page 33
Image 33
Table PD-34 — 7½ Ton

Performance

Data(7½Ton)

Table PD-34 — 7½ Ton

Heating Capacities (Net) WSC090A

At 3000 CFM

Downflow Configuration

Outdoor

 

IntegratedHeatingCapacity(Btuh/1000)

 

 

 

Total Power in Kilowatts at

 

 

Temp.

 

at Indicated Indoor Dry Bulb Temp.1

 

 

 

Indicated Indoor Dry Bulb Temp.

 

 

F.

60

70

75

80

 

60

70

75

80

 

-8

33.3

31.8

31.2

30.9

 

6.9

7.2

7.4

7.7

 

-3

36.3

35.0

34.5

34.2

 

6.9

7.2

7.4

7.7

 

2

39.7

38.4

38.0

37.7

 

6.9

7.2

7.5

7.8

 

7

43.2

42.2

41.7

41.4

 

6.9

7.3

7.6

7.9

 

12

47.0

45.9

45.5

45.2

 

6.9

7.4

7.6

7.9

 

17

51.1

50.1

49.7

49.3

 

7.0

7.4

7.7

8.0

 

22

55.4

54.4

54.0

53.6

 

7.0

7.5

7.8

8.1

 

27

60.2

59.1

58.6

58.2

 

7.1

7.6

7.9

8.3

 

32

65.3

64.1

63.6

63.1

 

7.2

7.7

8.0

8.4

 

37

70.4

69.1

68.5

68.0

 

7.3

7.8

8.2

8.5

 

42

75.6

74.3

73.6

73.0

 

7.4

8.0

8.3

8.7

 

47

90.2

88.6

87.8

87.0

 

7.5

8.1

8.5

8.8

 

52

96.7

94.9

94.0

93.2

 

7.6

8.2

8.6

9.0

 

57

103.4

101.4

100.5

99.5

 

7.8

8.4

8.8

9.2

 

62

110.2

108.1

107.0

106.0

 

7.9

8.6

9.0

9.4

 

67

117.2

114.8

113.6

112.5

 

8.1

8.8

9.2

9.6

 

72

124.3

121.7

120.5

119.1

 

8.3

9.0

9.4

9.8

 

For other airflow conditions, see heating capacity correction factor (Table PD-39).

Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions,subtract fan heat at this condition and add fan heat at new condition.

Note:

1.Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

Table PD-35— 7½ Ton Heating Capacities (Net) WSC090A At 3000 CFM Horizontal Configuration

Outdoor

IntegratedHeatingCapacity(Btuh/1000)

 

 

 

Total Power in Kilowatts at

 

 

Temp.

at Indicated Indoor Dry Bulb Temp.1

 

 

 

Indicated Indoor Dry Bulb Temp.

 

 

F.

60

70

75

80

 

60

70

75

80

 

-8

33.7

32.2

31.7

31.3

 

7.0

7.3

7.5

7.7

 

-3

36.8

35.4

34.9

34.6

 

7.0

7.3

7.5

7.8

 

2

40.1

38.8

38.4

38.1

 

7.0

7.3

7.6

7.8

 

7

43.6

42.5

42.1

41.8

 

7.0

7.4

7.6

7.9

 

12

47.4

46.3

45.9

45.6

 

7.0

7.4

7.7

8.0

 

17

51.4

50.4

50.0

49.7

 

7.1

7.5

7.8

8.1

 

22

55.8

54.7

54.3

53.9

 

7.1

7.6

7.9

8.2

 

27

60.5

59.4

58.9

58.4

 

7.2

7.7

8.0

8.3

 

32

65.5

64.4

63.8

63.3

 

7.3

7.8

8.1

8.4

 

37

70.6

69.4

68.8

68.2

 

7.3

7.9

8.2

8.6

 

42

75.8

74.5

73.8

73.2

 

7.4

8.0

8.4

8.7

 

47

90.4

88.8

88.0

87.2

 

7.6

8.2

8.5

8.9

 

52

96.9

95.1

94.2

93.3

 

7.7

8.3

8.7

9.1

 

57

103.5

101.5

100.6

99.6

 

7.8

8.5

8.8

9.2

 

62

110.3

108.1

107.1

106.0

 

8.0

8.6

9.0

9.4

 

67

117.2

114.9

113.7

112.5

 

8.2

8.8

9.2

9.6

 

72

124.3

121.7

120.5

119.2

 

8.3

9.0

9.4

9.8

 

For other airflow conditions, see heating capacity correction factor (Table PD-39).

Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.

Note:

1.Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

PKGP-PRC003-EN

33

Page 33
Image 33
Trane PKGP-PRC003-EN manual Performance, Data7½Ton, At 3000 CFM, Downflow Configuration, Table PD-34- 7½ Ton

FAQ

What is the heating capacity of the Trane 7 Ton Heat Pump model PKGP-PRC003-EN?

You can find the heating capacities and power at different temperatures and airflow conditions for the Trane 7 Ton Heat Pump model PKGP-PRC003-EN in the provided tables. Net heating capacity and power input includes indoor fan heat at ARI esp. Integrated heating capacities and powers include the effects of defrost in the frost region.

How does the Trane 7 Ton Heat Pump perform at different temperature and airflow conditions?

The performance of the Trane 7 Ton Heat Pump model PKGP-PRC003-EN at various temperature and airflow conditions is detailed in the tables, providing comprehensive information about heating capacities and power at different settings.

What factors are considered in the performance data of the Trane 7 Ton Heat Pump?

Factors such as net heating capacity, power input, and the effects of defrost in the frost region are included in the performance data for the Trane 7 Ton Heat Pump model PKGP-PRC003-EN. All information is at 70% OD relative humidity and demand defrost cycle.