Field Installed Options

Mechanical Specifications

Frostat

This option is to be utilized as a safety device.The Frostat opens when temperatures on the evaporator coil fall below 10°F. The temperature will need to rise to 50°F before closing.This option should be utilized in low airflow or high outside air applications.

LonTalk® Communication Interface This option shall be provided to allow the unit to communicate as aTracer™LCI-R device or directly with generic LonTalk Network Building Automation System Controls.

Oversized Motors

Direct drive oversized motors shall be available for high static applications.

Reference or Comparative Enthalpy Reference Enthalpy is used to measure and communicate outdoor humidity.The unit receives and uses this information to provide improved comfort cooling while using the economizer. Comparative Enthalpy measures and communicates humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or Comparative Enthalpy option shall be available when a factory or field installed Downflow Economizer is ordered.This option is available on all downflow models.

Tool-less Hail Guards

Tool-less, hail protection quality coil guards are available for condenser coil protection.

Trane Communication Interface

This option shall be provided to interface ReliaTel™ controlled units with theTrane Integrated ComfortTM systems.

Field Installed Options

CO2 Sensing

The CO2 sensor shall have the ability to monitor space occupancy levels within the building by measuring the parts per million of CO2 (Carbon Dioxide) in the air. As the CO2 levels increase, the outside air damper modulates to meet the CO2 space ventilation requirements.

Digital Display Zone Sensor

The Digital LCD (Liquid Crystal Display) zone sensor has the look and functionality of standard zone sensors.This sensor includes a digital display of set point adjustment and space temperature in F (Fahrenheit) or C (Celsius). Includes FAN and SYSTEM buttons (supports the service functions of the standard sensor). E-squared memory stores last programmed set points. Requires 24VAC (Volts AC).This sensor should be utilized with ReliaTel™ controls.

DualThermistor Remote Zone Sensor This sensor will allow the customer to reduce the total number of remote sensors to obtain space temperature averaging. This sensor should be utilized with ReliaTel controls.

High Static Drive

The high static drive option shall allow the standard motor on the 6 and 7½ ton units to operate with improved external static capabilities.

Manual Outside Air Damper

This rain hood and screen shall provide up to 50 percent outside air.

Motorized Outside Air Dampers Manually set outdoor air dampers shall provide up to 50 percent outside air. Once set, outdoor air dampers shall open to set position when indoor fan starts.The damper shall close to the full closed position when indoor fan shuts down.

Powered Exhaust

The powered exhaust, available for 6-10 ton units, shall provide exhaust of return air, when using an economizer, to maintain better bulding pressurization.

Remote Potentiometer

The minimum position setting of the economizer shall be adjusted with this accessory.

Roof Curb

The roof curb shall be designed to mate with the unit’s downflow supply and return and provide support and a water tight installation when installed properly. The roof curb design shall allow field- fabricated rectangular supply/return ductwork to be connected directly to the curb. Curb design shall comply with NRCA requirements. Curb shall be shipped knocked down for field assembly and shall include wood nailer strips.

Thermostat

Two stage heating and cooling operation or one stage heating and cooling shall be available in either manual or automatic changeover. Automatic programmable electronic with night set back shall also be available.

Ventilation Override Accessory

With the Ventilation Override Accessory installed, the unit can be set to transition up to 3 different pre-programmed sequences for Smoke Purge, Pressurization, and Exhaust.The transition occurs when a binary input on the RTOM is closed (shorted).This would typically be a hard wired relay output from a smoke detector or fire control panel.The ventilation override accessory shall be available as field installed.

Zone Sensor

This control shall be provided to interface with the Micro equipped units and shall be available in either manual, automatic programmable with night setback, with system malfunction lights, or remote sensor options.

PKGP-PRC003-EN

55

Page 55
Image 55
Trane PKGP-PRC003-EN manual Field Installed Options, Mechanical Specifications

FAQ

What is the purpose of Frostat?

Frostat is utilized as a safety device, opening when temperatures on the evaporator coil fall below 10F and closing when they rise to 50F. It should be used in low airflow or high outside air applications.

What is the function of CO2 Sensing?

The CO2 sensor monitors space occupancy levels by measuring the parts per million of CO2 in the air, modulating the outside air damper to meet the ventilation requirements as CO2 levels increase.

How does the High Static Drive option improve operation?

The high static drive option allows the standard motor on certain units to operate with improved external static capabilities.