Trane PKGP-PRC003-EN manual Performance, Data4Ton, Heating Capacities Net WSC048A1 At 1600 CFM

Models: PKGP-PRC003-EN

1 56
Download 56 pages 28.86 Kb
Page 30
Image 30
Table PD-28 — 4Ton Three Phase

Performance

Data(4Ton)

Table PD-28 — 4Ton Three Phase

Heating Capacities (Net) WSC048A1 At 1600 CFM

 

 

 

 

 

 

 

Outdoor

InstantaneousHeatingCapacity(Btuh/1000)

 

 

IntegratedHeatingCapacity(Btuh/1000)

Total Power in Kilowatts at

Temp.

 

 

at Indicated Indoor Dry Bulb Temp.

 

 

 

at Indicated Indoor Dry Bulb Temp.1

 

 

Indicated Indoor Dry Bulb Temp.

 

F.

60

70

75

80

60

70

75

80

 

60

70

75

80

 

-8

17.2

16.9

16.8

16.6

15.5

15.2

15.1

14.9

 

3.78

4.11

4.30

4.51

 

-3

19.5

19.0

18.9

18.8

17.6

17.1

17.0

16.9

 

3.73

4.07

4.26

4.49

 

2

21.8

21.3

21.1

21.0

19.6

19.2

19.0

18.9

 

3.82

4.14

4.34

4.55

 

7

24.4

23.8

23.5

23.3

22.0

21.4

21.2

21.0

 

3.86

4.18

4.38

4.59

 

12

27.0

26.3

26.0

25.8

24.3

23.7

23.4

23.2

 

3.90

4.23

4.43

4.63

 

17

29.8

29.0

28.7

28.4

26.8

26.1

25.8

25.6

 

3.96

4.28

4.48

4.68

 

22

32.7

31.8

31.4

31.1

29.4

28.6

28.3

28.0

 

4.01

4.34

4.53

4.74

 

27

35.7

34.7

34.3

33.9

32.1

31.2

30.9

30.5

 

4.07

4.39

4.59

4.79

 

32

38.8

37.7

37.3

36.8

34.9

33.9

33.6

33.1

 

4.13

4.46

4.65

4.85

 

37

41.8

40.7

40.2

39.7

37.6

36.6

36.2

35.7

 

4.19

4.52

4.72

4.92

 

42

44.9

43.8

43.2

42.7

40.4

39.4

38.9

38.4

 

4.26

4.60

4.79

4.99

 

47

48.1

46.8

46.2

45.6

48.1

46.8

46.2

45.6

 

4.33

4.68

4.87

5.07

 

52

51.3

49.9

49.2

48.6

51.3

49.9

49.2

48.6

 

4.42

4.76

4.95

5.15

 

57

54.4

52.9

52.2

51.5

54.4

52.9

52.2

51.5

 

4.51

4.85

5.04

5.24

 

62

57.5

55.9

55.1

54.3

57.5

55.9

55.1

54.3

 

4.60

4.95

5.14

5.34

 

67

57.3

55.5

54.6

53.7

57.3

55.5

54.6

53.7

 

4.58

4.92

5.10

5.29

 

72

60.5

58.5

57.6

56.7

60.5

58.5

57.6

56.7

 

4.70

5.04

5.22

5.42

 

For other airflow conditions, see heating capacity correction factor (Table PD-39).

Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition. Note:

1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

Table PD-29 — 4 Ton Single Phase
Heating Capacities (Net) WSC048A3,A4,AW

At 1600 CFM

 

 

 

 

 

Outdoor

 

InstantaneousHeatingCapacity(Btuh/1000)

 

 

IntegratedHeatingCapacity(Btuh/1000)

Total Power in Kilowatts at

Temp.

 

 

at Indicated Indoor Dry Bulb Temp.

 

 

 

at Indicated Indoor Dry Bulb Temp.1

 

 

Indicated Indoor Dry Bulb Temp.

F

 

60

70

75

80

 

60

70

75

80

 

60

70

75

80

 

-8

17.4

17.0

16.8

16.6

15.7

15.3

15.1

14.9

 

3.61

3.99

4.22

4.48

 

-3

19.5

19.1

18.8

18.6

17.6

17.2

16.9

16.7

 

3.57

3.96

4.20

4.48

 

2

21.9

21.3

21.2

21.1

19.7

19.2

19.1

19.0

 

3.65

4.02

4.24

4.50

 

7

24.3

23.7

23.5

23.4

21.9

21.3

21.2

21.1

 

3.69

4.05

4.27

4.52

 

12

27.0

26.3

26.1

25.9

24.3

23.7

23.5

23.3

 

3.73

4.09

4.31

4.54

 

17

29.7

28.9

28.7

28.5

26.7

26.0

25.8

25.7

 

3.78

4.14

4.35

4.58

 

22

32.5

31.7

31.4

31.1

29.3

28.5

28.3

28.0

 

3.83

4.19

4.40

4.62

 

27

35.5

34.6

34.3

33.9

32.0

31.1

30.9

30.5

 

3.89

4.24

4.45

4.67

 

32

38.6

37.7

37.3

36.9

34.7

33.9

33.6

33.2

 

3.95

4.30

4.51

4.72

 

37

41.7

40.7

40.2

39.8

37.5

36.6

36.2

35.8

 

4.01

4.37

4.57

4.78

 

42

44.8

43.7

43.2

42.7

40.3

39.3

38.9

38.4

 

4.08

4.44

4.64

4.85

 

47

48.0

46.8

46.3

45.7

48.0

46.8

46.3

45.7

 

4.16

4.52

4.72

4.93

 

52

51.2

49.9

49.3

48.7

51.2

49.9

49.3

48.7

 

4.25

4.61

4.81

5.01

 

57

54.4

53.0

52.3

51.7

54.4

53.0

52.3

51.7

 

4.35

4.71

4.90

5.10

 

62

57.6

56.0

55.3

54.5

57.6

56.0

55.3

54.5

 

4.45

4.81

5.00

5.20

 

67

57.4

55.7

54.8

53.9

57.4

55.7

54.8

53.9

 

4.45

4.79

4.97

5.16

 

72

60.7

58.8

57.9

57.0

60.7

58.8

57.9

57.0

 

4.58

4.93

5.11

5.30

 

For other airflow conditions, see heating capacity correction factor (Table PD-39).

Net heating capacity and power input includes indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition. Note:

1. Integrated heating capacities and powers include the effects of defrost in the frost region. All heating capacities and power (kw) are at 70% OD relative humidity and demand defrost cycle.

30

PKGP-PRC003-EN

Page 30
Image 30
Trane PKGP-PRC003-EN Performance, Data4Ton, Heating Capacities Net WSC048A1 At 1600 CFM, Table PD-28- 4Ton Three Phase

FAQ

What heating capacities and power input data is available for Trane PKGP-PRC003-EN model heat pump?

Table PD-28 and Table PD-29 provide detailed heating capacities and power input data for different temperature and airflow conditions, including the effects of defrost and indoor fan heat.

How are net heating capacities and power input calculated for the Trane heat pump model PKGP-PRC003-EN?

The net heating capacities and power input include the effects of defrost in the frost region, as well as indoor fan heat at ARI esp. To obtain net heating at other conditions, subtract fan heat at the current condition and add fan heat at the new condition.

Where can I find information about airflow conditions for Trane heat pump model PKGP-PRC003-EN?

The data for other airflow conditions can be found in the heating capacity correction factor Table PD-39, which complements Table PD-28 and Table PD-29.