Trane PKGP-PRC003-EN Data10 Ton, Performance, Table PD-18- Continued, Table PD-19- Continued

Models: PKGP-PRC003-EN

1 56
Download 56 pages 28.86 Kb
Page 26
Image 26
Data(10 Ton)

Performance

Data(10 Ton)

Table PD-18 — Belt Drive Evaporator Fan Performance — 10-Ton — WSC120A3,A4,AW — Downflow Airflow

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

 

.50

 

.60

 

.70

.80

 

.90

 

1.00

CFM

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

2-HP Standard Motor & Field Supplied Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

3200

560

0.53

601

0.63

644

0.74

682

0.85

718

0.97

754

1.10

789

1.25

822

1.38

856

1.53

887

1.67

3600

620

0.73

657

0.83

694

0.95

731

1.08

764

1.20

797

1.33

829

1.48

860

1.63

892

1.79

922

1.95

4000

 

680

0.97

715

1.09

747

1.21

782

1.35

814

1.49

844

1.63

874

1.77

903

1.93

932

2.09

960

2.27

4400

741

1.27

773

1.40

803

1.53

834

1.67

864

1.82

894

1.98

922

2.13

948

2.28

975

2.44

1001

2.62

4800

803

1.62

833

1.76

861

1.90

887

2.04

916

2.20

972

2.55

997

2.71

1022

2.87

1046

3.04

 

 

 

 

2-HP Standard Motor & Drive

 

 

 

 

 

 

 

5-HP Oversized Motor & Drive

 

 

Table PD-18 — Continued

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

1.10

 

1.20

 

1.30

 

1.40

1.50

1.60

 

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

2-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

3200

917

1.82

945

1.97

973

2.14

999

2.30

1024

2.47

1048

2.65

1072

2.82

1095

3.00

1117

3.17

1140

3.36

3600

951

2.11

979

2.27

1007

2.43

1033

2.60

1059

2.78

1082

2.95

1107

3.14

1130

3.33

1152

3.52

1173

3.71

4000

988

2.44

1015

2.62

1042

2.79

1068

2.97

1093

3.15

1117

3.33

1142

3.52

1164

3.70

1187

3.91

1209

4.11

4400

1028

2.81

1053

3.00

1078

3.19

1103

3.38

1128

3.57

1152

3.77

1176

3.96

1198

4.15

1221

4.36

1243

4.56

4800

1071

3.23

1095

3.42

1119

3.62

1142

3.83

1166

4.04

1189

4.25

1212

4.46

1233

4.66

1256

4.88

1277

5.09

 

 

 

 

 

 

 

 

 

 

5-HP Oversized Motor & Drive

 

 

 

 

 

 

For Standard Evaporator Fan Speed (RPM), reference Table PD-20. Notes:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories.

2-HP Fan Motor Heat (MBH) = 2.00 x Fan BHP + .500.

5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.

1. Field Supplied Motor Sheave 1VP34 x 7/8”, Fan Sheave AK69,and belt AX35 required.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-19— Belt Drive Evaporator Fan Performance — 10-Ton — WSC120A3,A4,AW — Horizontal Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

.20

.30

 

 

.40

.50

 

 

.60

 

.70

.80

 

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

2-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

 

 

 

3200

656

0.81

691

0.89

730

1.00

771

1.13

807

1.26

844

1.39

886

1.55

926

1.72

965

1.89

1000

2.06

3600

729

1.13

761

1.22

792

1.32

829

1.45

865

1.60

898

1.74

930

1.89

965

2.06

1002

2.24

1038

2.43

4000

802

1.52

833

1.63

860

1.73

890

1.86

923

2.01

956

2.17

986

2.30

1015

2.48

1044

2.65

1077

2.85

4400

876

1.99

905

2.12

931

2.24

955

2.35

983

2.49

1014

2.66

1045

2.84

1072

3.01

1098

3.18

1125

3.36

4800

950

2.56

977

2.70

1002

2.84

1025

2.96

1048

3.08

1074

3.24

1102

3.43

1131

3.63

1156

3.81

1181

4.00

 

 

 

 

 

 

 

 

 

 

5-HP Oversized Motor & Drive

 

 

 

 

 

 

2-HP Standard Motor & Field Supplied Low Static Drive (1)

Table PD-19 — Continued

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

1.10

 

1.20

 

1.30

 

1.40

1.50

1.60

 

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

5-HP Oversized Motor & Drive

 

 

 

 

 

 

 

 

 

3200

1029

2.20

1057

2.35

1084

2.49

1108

2.63

1132

2.77

1155

2.91

1177

3.05

1198

3.18

1219

3.32

1239

3.46

3600

1072

2.62

1106

2.81

1134

2.98

1160

3.15

1185

3.31

1209

3.47

1231

3.63

1252

3.78

1274

3.94

1295

4.10

4000

1111

3.05

1143

3.26

1174

3.47

1204

3.68

1232

3.88

1260

4.09

1283

4.27

1306

4.46

1327

4.63

1349

4.81

4400

1152

3.55

1182

3.76

1211

3.99

1241

4.21

1270

4.44

1299

4.68

1327

4.91

1352

5.14

1377

5.37

1400

5.57

4800

1205

4.19

1229

4.39

1253

4.58

1280

4.81

1309

5.06

1336

5.31

1363

5.56

 

 

 

 

 

 

 

 

 

 

 

 

5-HP Oversized Motor& Field Supplied Sheave (2)

 

 

For Standard Evaporator Fan Speed (RPM), reference Table PD-20. Notes:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-23 to determine additional static pressure drop due to other options/accessories. 2-HP Fan Motor Heat (MBH) = 3.00 x Fan BHP + .500.

5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.

1.Field Supplied Motor Sheave 1VP34 x 7/8”, Fan Sheave AK69, and belt AX35 required.

2.Field supplied Fan Sheave BK95 required.

Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

26

PKGP-PRC003-EN

Page 26
Image 26
Trane PKGP-PRC003-EN manual Data10 Ton, Performance, Table PD-18- Continued, Table PD-19- Continued

FAQ

What is included in the data for the Trane 10 Ton Heat Pump models PKGP-PRC003-EN?

The data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

What are the fan motor heat calculations for the Trane 10 Ton Heat Pump models PKGP-PRC003-EN?

For a 2-HP fan motor, the heat calculation is 2.00 x Fan BHP + .500. For a 0.5-HP fan motor, the heat calculation is 2.950 x Fan BHP + .470.

What are the requirements for field supplied motor and fan sheaves for the Trane 10 Ton Heat Pump models PKGP-PRC003-EN?

For field supplied motor, the requirement is 1VP34 x 7/8, and for fan sheave, the requirement is AK69. Belt AX35 is also required.