Optional Belt Drive Indoor Motor

Electrical

Data

Table ED-4— Unit Wiring With Electric Heat (Single Point Connection) — Optional Belt Drive Indoor Motor

 

 

 

 

 

 

Optional Belt Drive Indoor Motor

 

To Use

Heater

Heater

Control

 

 

 

 

 

 

Max Fuse Size or

 

Tons

With

Model No.

KW Rating1

Stages

MCA

Max Circuit Breaker2

 

 

 

208/230 Volts Three Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRR306A

4.5/6.0

1

37.4/39.8

45/45

 

3

WSC036A3

BAYHTRR312A

9.0/12.0

2

53.0/57.9

60/60

 

 

 

BAYHTRR318A

13.1/17.4

2

67.1/74.1

70/80

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRR306A

4.5/6.0

1

41.4/43.8

50/50

 

4

WSC048A3

BAYHTRR312A

9.0/12.0

2

57.0/61.9

60/70

 

 

BAYHTRR318A

13.1/17.4

2

71.1/78.1

80/80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTR306A

4.5/6.0

1

47.0/49.4

60/60

 

5

WSC060A3

BAYHTRR312A

9.0/12.0

2

62.6/67.5

70/70

 

 

BAYHTRR318A

13.1/17.4

2

76.8/83.8

80/90

 

 

 

 

 

 

BAYHTRR323A

17.3/23.0

2

91.4/100.5

100/110

 

 

 

 

460 Volts Three Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRR406A

6.0

1

20.3

25

 

3

WSC036A4

BAYHTRR412A

12.0

2

29.3

30

 

 

 

BAYHTRR418A

17.4

2

37.4

40

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRR406A

6.0

1

21.9

25

 

4

WSC048A4

BAYHTRR412A

12.0

2

30.9

35

 

 

 

BAYHTRR418A

17.4

2

39.1

40

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRR406A

6.0

1

25.2

30

 

5

WSC060A4

BAYHTRR412A

12.0

2

34.2

40

 

 

 

BAYHTRR418A

17.4

2

42.3

45

 

 

 

BAYHTRR423A

23.0

2

50.8

60

 

 

 

 

575 Volts Three Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRRW06A

6.0

1

16.2

20

 

4

WSC036AW

BAYHTRRW12A

12.0

2

23.3

25

 

 

BAYHTRRW18A

17.4

2

29.8

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRRW06A

6.0

1

17.6

20

 

4

WSC048AW

BAYHTRRW12A

12.0

2

24.7

25

 

 

BAYHTRRW18A

17.4

2

31.2

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRRW06A

6.0

1

19.9

20

 

5

WSC060AW

BAYHTRRW12A

12.0

2

27.1

30

 

 

BAYHTRRW18A

17.4

2

33.6

35

 

 

 

 

 

 

BAYHTRRW23A

23.0

2

40.3

45

 

 

 

 

 

 

 

 

 

 

Notes:

1.Heater kw ratings are at 208/240 for 208/230V unit

2.HACR type circuit breaker per NEC.

PKGP-PRC003-EN

41

Page 41
Image 41
Trane PKGP-PRC003-EN manual Electrical Data, Optional Belt Drive Indoor Motor

FAQ

What is the max fuse size for BAYHTRR306A heater?

The max fuse size for the BAYHTRR306A heater is 45/45 for 208/230 volts three phase units.

What are the MCA and max circuit breaker for a WSC048A3 unit with BAYHTRR312A heater?

The MCA is 57.0/61.9 and the max circuit breaker is 60/70 for 3-ton units.

How do I choose the correct heater for my Trane heat pump?

To choose the correct heater for a Trane heat pump, refer to the model number and KW rating in the electrical data table.