Trane ZN510 Controller, Tracer manual Manual Output Testing the Heat, Pump Configurations

Models: ZN510 Controller Tracer

1 32
Download 32 pages 37.14 Kb
Page 23
Image 23

Troubleshooting

Manual Output Testing the Heat

for at least three seconds to

Pump Configurations

start the test mode.

The procedure for testing heat pump

2. The test sequence resets

configurations is:

diagnostics and turns off all

 

1. Press and hold the Test button

outputs.

 

Table 12: Test sequence

3.Press the Test button several more times (no more than once per second) to advance through the test sequence.

 

Step

 

Fan

Reversing Valve

Compr 1

Compr 2

Damper

 

 

BOP 1

BOP 2

BOP 4

BOP 5

BOP 6

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Off

 

Off

Off

Off

Off

Closed

 

 

 

 

 

 

 

 

 

2. Fan on (At the beginning of step 2, the

 

On

Off

Off

Off

Closed

 

controller attempts to clear all diagnostics).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Reversing Valve

 

On

On

Off

Off

Closed

 

 

 

 

 

 

 

 

 

4. Cool 1

 

On

On

On

Off

Closed

 

 

 

 

 

 

 

 

 

5. Cool 2

 

On

On

On

On

Closed

 

 

 

 

 

 

 

 

 

6. Compressor(s) off

 

 

 

 

 

 

 

This stage helps avoid compressor cooling

 

 

 

 

 

 

 

and heating in sequential steps by turning the

 

On

Off

Off

Off

Closed

 

compressors off prior to changing the

 

 

 

 

 

 

 

reversing valve state.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7. Heat 1

 

On

Off

On

Off

Closed

 

 

 

 

 

 

 

 

 

8. Heat 2

 

On

Off

On

On

Closed

 

 

 

 

 

 

 

 

 

9. Outdoor air damper

 

On

Off

Off

Off

Open

 

 

 

 

 

 

 

 

 

10. Exit

 

 

 

 

 

 

 

After the outdoor air damper step, the test

 

 

 

 

 

 

 

 

sequence performs the exit step. This

 

 

 

 

 

 

 

 

initiates a reset and attempts to return the

 

 

 

 

 

 

 

 

controller to normal operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Testing the Heat Pump

Configurations

The outputs are not subject to minimum times during the test sequence. However, the test sequence only permits one step per second which limits output time.

All outputs are exercised regardless what timer they are or are not configured for. For example, single compressor heat pumps function

the same as two compressor units. For single compressor units, the cool 2 and heat 2 steps control the appropriate binary outputs, but do not affect unit operation.

Reversing valve and damper outputs cycle independent of configuration.

Pump Operation for

Systems with ZN510

Loop Controller

During Unoccupied, the pumps will be OFF but should be energized to test compressor operation. The user must override the pumps either at the ZN510 Loop Controller or by pushing the ON button of the zone sensor. This will send the units to an occupied bypass, which will turn the

pumps on prior to operating manual output test.

23

Page 23
Image 23