Zone Sensor

Zone Sensor

The ZN510 controller accepts the following zone sensor inputs:

zSpace temperature mea- surement.

zLocal setpoint (internal or external on the zone sensor).

zFan switch. (Optional)

zTimed override (ON and CANCEL).

zCommunication Jack.

If both hardwired and communicated space temperature

values exist, the controller ignores the hardwired space temperature input and uses the communicated value.

Internal and External Setpoint Adjustment

Zone sensors with an internal or external setpoint adjustment provide the ZN510 controller with a local setpoint (50 to 85 F or 10 to 29.4 C). The internal setpoint adjustment is concealed under the zone sensor’s cover. To reveal the adjustable setpoint wheel, remove the zone sensor cover. The external setpoint

(when present) is exposed on the zone sensor’s front cover.

When the hardwired setpoint adjustment is used to determine the setpoints, all unit setpoints are calculated based on the hardwired setpoint values, the configured setpoints, and the active mode of the controller.

Setpoint Operation

The controller has three methods of heating and cooling setpoints operation. See Table 5 for the methods of setpoint operation.

Table 5: Methods of setpoint operation.

Method

Situation used

 

 

Zone Sensor

A hardwired, adjustable setpoint is connected to the controller. Local setpoints are

(with an adjustable hardwired

enabled in the unit configuration. No communicated setpoint is present.

setpoint)

 

 

 

 

A setpoint is communicated to the unit controller (typically from a building automation

 

system or a peer controller). If both a hardwired setpoint and a communicated setpoint

Communicated source

exist, the controller uses the communicated value. The configuration feature for enabling

or disabling the local setpoint does not affect the setpoint handling when communicated

 

 

setpoints are used. The communicated setpoint always takes priority over the hardwired

 

setpoint, even when the local setpoint is enabled.

 

 

 

The controller uses the locally stored default heating and cooling setpoints when neither

 

a local hardwired setpoint or communicated setpoint is present. When a building

 

automation system is present, the controller uses the default setpoints when no setpoint

Stored default setpoints

is communicated to the controller and no hardwired setpoint exists. The controller uses

 

stored default setpoints when only a local setpoint exists, but the local setpoint is

 

disabled in the configuration of the controller. The controller always uses the stored

 

default (unoccupied) setpoints in unoccupied mode.

 

 

15