Unit Operation

Power

The ZN510 controller is powered by 24 VAC. A total of two 1/4-inch quick- connect terminals are provided for 24 VAC connection to the board. See Figure 4 for ZN510 power requirement.

Note: Power for field installed ancil- lary devices is not available from the board. It must be tapped at trans- former. See Table 21 for excess power available.

Factory Supplied Transformer

Line

Voltage

24VAC

Figure 4: Power Connections

Binary Outputs

The ZN510 uses five of its binary outputs to control heat pump units. Outputs are load side switching triacs. The triac acts as a switch by either making or breaking the circuit between the load (reversing valve, damper, contactor, relay) and ground.

See Figure 5 for the configuration of the five binary outputs.

2-Position Damper Actuator or

 

Generic Binary Output

 

Binary output 6 (BOP 6) is factory

 

configured to control a normally

 

closed 2-position outdoor air damper.

 

It may be field modified to control a

 

generic output for control by a

 

building automation system. If set up

 

as a generic output, the controller

 

does not use BOP 6 as part of the

Figure 5: Binary outputs

normal control. A building automation

 

system must issue commands to

 

control the generic binary output.

.

 

 

BOP 2 (ReversingValve)

BOP 3 (Not available)

 

 

BOP 5 (Compressor 1)

BOP 6 (Compressor 2)

 

Field installed

 

 

 

 

2 position

 

BOP 4 (Not Used)

 

 

damper actuator

 

 

24VAC

BOP 1 (Fan)

 

 

1TB1-17

 

BOP 7

1TB1-18

 

 

J1-1

J1-2

J1-3

 

J1-4

J1-5

J1-6

J1-7

 

 

 

Binary Outputs

 

Note:

zDuring occupied mode, the outdoor air damper is closed when the fan is controlled off.

zDuring unoccupied mode, the outdoor air damper normally remains closed.

z2-position damper must not exceed 10 VA power output from board.

Table 1: BOP 6 control of a 2-position outdoor air damper

Model

Fan Operation

Outdoor Air Damper

 

 

 

Occupied

On or cycling

Open

Off

Closed

 

 

 

 

Occupied warm up or

On or cycling

Closed

cool down

 

 

 

 

 

Occupied standby

On or cycling

Closed

 

 

 

Unoccupied

Cycling

Closed

 

 

 

Diagnostic present

Diagnostic dependent

Closed

 

 

 