Trane Tracer, ZN510 Controller manual Binary Inputs, Description Terminals Function Range

Models: ZN510 Controller Tracer

1 32
Download 32 pages 37.14 Kb
Page 32
Image 32

Hardware

Specifications

Table 18: Binary Inputs

Description

Terminals

Function

Binary Input 1

J2-1

24 VAC

 

 

 

 

 

 

 

 

J2-2

Input

 

 

 

 

 

 

 

Binary Input 2

J2-3

24 VAC

 

 

 

 

 

 

 

 

J2-4

Input

 

 

 

 

 

 

 

Binary Input 3

J2-5

24 VAC

 

 

 

 

 

 

 

 

J2-6

Input

 

 

 

 

 

 

 

Table 19: Binary Outputs

 

 

 

 

 

 

 

 

Description

Terminals

Output

Load Energized

Load De-energized

Rating

 

 

 

 

 

 

 

 

 

Binary Output 1

J1-1

12 VA

1 VAC RMS (typical)

24 VAC RMS (typical)

 

 

 

 

 

Binary Output 2

J1-2

12 VA

1 VAC RMS (typical)

24 VAC RMS (typical)

 

 

 

 

 

Binary Output 3

J1-4

NOT USED

 

 

 

 

 

 

 

Binary Output 4

J1-5

12 VA

1 VAC RMS (typical)

24 VAC RMS (typical)

 

 

 

 

 

Binary Output 5

J1-6

12 VA

1 VAC RMS (typical)

24 VAC RMS (typical)

 

 

 

 

 

Binary Output 6

J1-7

12 VA

1 VAC RMS (typical)

24 VAC RMS (typical)

 

 

 

 

 

Table 20: Analog Inputs

Description

Terminals

Function

Range

 

 

 

 

Zone

TB3-1

Zone temperature input

5 to 122 F (-15 to 50 C)

 

 

 

 

Ground

TB3-2

Analog ground

NA

 

 

 

 

Set

TB3-3

Setpoint input

40 to 115 F (4.4 to 46.1 C)

 

 

 

 

Fan

TB3-4

Fan switch input

OFF = 4821 to 4919 Ohms

 

 

 

AUTO = 2297 to 2342 Ohms

 

 

 

 

Ground

TB3-6

Analog ground

NA

 

 

 

 

Analog Input 1

J3-1

Leaving water

-40 to 212 F (-40 to 100 C)

 

 

temperature

 

 

 

 

 

 

J3-2

Analog ground

NA

 

 

 

 

Analog Input 2

J3-3

Discharge air temperature

-40 to 212 F (-40 to 100 C)

 

 

 

 

 

J3-4

Analog ground

NA

 

 

 

 

32

Page 32
Image 32
Trane Tracer manual Binary Inputs, Description Terminals Function, Binary Output J1-1 12 VA VAC RMS typical J1-2 J1-4