Power Up Sequence

Power Up Sequence

When 24 VAC power initially is applied to the ZN510 controller, the following sequence occurs:

1.All outputs are controlled off.

2.The controller reads all inputs to determine their initial values.

Note: Because the space tempera- ture can be hardwired to the con- troller or communicated, the controller waits for several minutes to check for the presence of a com- municated value.

3.A random start time is hard coded on every board and cannot be disabled. The board generates a random time delay between 0 and 25 seconds. Once this time expires, the power up control wait time (if configured) will wait for 120 seconds. The power up control wait allows ample time for a communicated request to arrive. If the power up control wait time expires, and the controller does not receive a communicated occupancy command, the unit assumes stand alone operation.

4.Normal operation begins.