Unit Operation

Output Overrides

The ZN510 controller includes a manual output test function. Use this feature to manually exercise the outputs in a defined sequence. The purpose of the test sequence, is to verify output and end device operation. Use the manual output test to:

zVerify output wiring and operation without using Trane’s service tool, Rover.

zForce compressor operation, allowing the technician to use refrigerant gauges or other test equipment to verify unit operation.

The test sequence resets unit diagnostics and attempts to restore normal unit operation prior to testing the outputs. If the diagnostics remains after a reset, the status LED indicates the diagnostic condition is still present and has affected the

manual output test. See Troubleshooting section for Green LED and Testing Heat Pump Configurations on page 21 & 22.

Analog Outputs

ZN510 does not use analog outputs.

Binary Inputs

The ZN510 controller has three available binary inputs (BI). These inputs are factory-configured for the following functions:

zBI 1= Low temperature detection (freezestat) (Circuit 2).

zBI 2 = Condensate overflow.

zBI 3 = Occupancy or generic binary input.

Each binary input may be configured as not used depending on options selected. BI 3 is configured as a normally open occupancy input, but may be field modified for generic binary input which is only supported by a build- ing automation system.

Low Temperature Detection (Circuit 2)

Condensate Overflow

Field Wired Occupancy Input

BI 1

BI 2

BI 3

J2-1

J2-2

J2-3

J2-4

J2-5

J2-6

Binary Inputs

Note:

The diagnostic functions related to binary inputs such as low tempera- ture detection and condensate overflow are fixed sequences.

Each binary input associates an input signal of 0 VAC with open contacts and 24 VAC with closed contacts. See Figure 6 for typical binary input configurations for the heat pump.

Figure 6: Binary inputs.

Table 2: Binary input configurations

Binary Input

Description

Configuratio

Contact

Contact

n

Closure

Open

 

 

 

 

 

 

 

BI 1

Low Temperature

Normally

Normal

Diagnostic

Detection (Cir 2)

closed

 

 

 

 

 

 

 

 

BI 2

Condensate Overflow

Normally

Normal

Diagnostic

closed

 

 

 

 

 

BI 3

Occupancy

Normally open

Unoccupied

Occupied

 

 

 

 

Generic

Normally open

Normal

Normal

 

 

 

 

 

 

Note:

See Page 10 for specific information concerning BI 1, BI 2 and BI 3.