Configuration
Configurable Parameters Rover, Trane’s service tool, uses the unit type “heat pump” to determine and download unit configuration
information, such as the default | default configurations for heat |
analog inputs, the default binary | pumps. |
inputs, and the default binary output |
|
configurations. See Table 7 for |
|
Table 8: Heat pump heating or cooling operation.
Unit Type |
| Heat pump |
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
Cooling Source | Compressor |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
Heating Source | Compressor (none for cooling only units) |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
Compressors | 1 (2 for |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
| BOP 1: Fan on (normally open) |
|
|
|
|
|
| ||
| BOP 2: Reversing valve (normally open)* |
|
|
|
|
|
| ||
Binary Outputs | BOP 3: Not used |
|
|
|
|
|
| ||
BOP 4: Compressor 1 (normally open) |
|
|
|
|
|
| |||
|
|
|
|
|
|
| |||
| BOP 5: Compressor 2 (normally open)** |
|
|
|
|
|
| ||
| BOP 6: Outdoor Air Damper (normally open)*** |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |||
| BI 1: Low temperature detection, circuit 2 (normally closed)* |
|
|
|
| ||||
Binary Inputs | ** |
|
|
|
|
|
|
|
|
BI 2: Condensate overflow (normally closed)† |
|
|
|
|
|
| |||
|
|
|
|
|
|
| |||
| BI 3: Occupancy (normally open) |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
| Zone: Space temperature (0.0 F calibration) |
|
|
|
|
|
| ||
| Set: Setpoint (0.0 F calibration) |
|
|
|
|
|
| ||
Analog Inputs | Fan: Fan mode |
|
|
|
|
|
| ||
| AI 1: Leaving water temperature |
|
|
|
|
|
| ||
| AI 2: Discharge air temperature |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
| Fan operation (heating): Cycling |
|
|
|
|
|
| ||
| Fan operation (cooling): Cycling |
|
|
|
|
|
| ||
Fan | Fan speed default (heating): On/high |
|
|
|
|
|
| ||
| Fan speed default (cooling): On/high |
|
|
|
|
|
| ||
| Fan switch (hardwired): Enabled |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| ||
| Unoccupied cooling setpoint: 85 F |
|
|
|
|
|
| ||
| Occupied standby cooling: 78 F |
|
|
|
|
|
| ||
|
|
|
| The heating and cooling setpoint |
|
| |||
| Occupied cooling setpoint: 74 F |
|
|
|
|
| |||
|
|
|
| high and low limits only apply to the |
|
| |||
| Occupied heating setpoint: 71 F |
|
|
|
|
| |||
|
|
|
| occupied and occupied standby |
|
| |||
| Occupied standby heating: 67 F |
|
|
|
|
| |||
|
|
|
| setpoints. These limits never apply |
|
| |||
Setpoints | Unoccupied heating setpoint: 60 F |
|
|
|
|
| |||
|
|
| to the unoccupied setpoints. |
|
| ||||
| Cooling setpoint high limit: 115 | F |
|
|
|
|
| ||
| Cooling setpoint low limit: 40 F |
|
|
|
|
|
|
| |
| Heating setpoint high limit: 115 | F |
|
|
|
|
|
| |
| Heating setpoint low limit: 40 F |
|
|
|
|
|
|
| |
|
|
| The occupied bypass time is used for timed |
| |||||
| Thumbwheel set point: Enabled |
|
|
| |||||
|
|
|
|
| override applications. The timed override |
| |||
Occupied Bypass |
|
|
|
| |||||
120 minutes |
|
|
| timer is maintained in the unit controller. |
| ||||
Timer |
|
|
|
| |||||
|
|
| |||||||
|
|
|
| When the timed override is applicable, the |
| ||||
|
|
|
|
|
| ||||
Leaving Water |
|
|
|
| |||||
|
|
|
| controller reports “Occupied Bypass” as its |
| ||||
Temperature | Unit specific (20 F ground source or 35 F standard) |
|
| ||||||
| effective occupancy mode. |
| |||||||
Low Limit |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| |
Location Identifier | Unit specific (maximum of 30 characters) |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
*BOP 2, BI1: Not used on cooling only units.
**BOP 5: Not used on signal compressor unit.
***Configured but not required.
† Optional model number dependent
The leaving water temperature low limit is used for freeze protection of circuit 1 on heat pumps. Circuit 2 is protected by a binary low temperature detection device (freezestat) with a fixed trip point.