Troubleshooting

Questionable Unit

Operation

Table 14: Compressor(s) not running

Probable Cause

Explanation

 

 

Normal operation.

The controller compressor(s) turn on and off to meet the unit capacity

requirements.

 

 

 

 

The desired operating mode (such as off, heat and cool) can be communicated to

Requested mode off.

the controller. When off is communicated to the controller, the unit shuts off all

 

unit compressor(s).

 

 

 

Numerous communicated requests may disable the compressor, including a

Communicated disable.

compressor enable input. Depending on the state of the communicated request,

 

the unit may disable the compressor.

 

 

 

The controller includes a manual output test sequence that may be used to verify

Manual output test.

output operation and associated output wiring. However, based on the current

step in the test sequence, the compressor(s) may not be on. Refer to the manual

 

 

output overrides on page 9.

 

 

 

A specific list o f diagnostics affects compressor operation, depending whether

Diagnostic present.

the unit is configured as heat pump. For more information, see the Diagnostics

 

section on page 27.

 

 

 

The controller must be properly configured based on the actual installed end

Unit configuration.

devices and application. When the unit configuration does not match the actual

 

end device, the compressor may not work correctly.

 

 

 

If the controller does not have power, the compressor does not operate. For the

No power to the controller.

ZN510 controller to operate normally, a voltage input of 24 VAC must be applied.

When the green LED is off continuously, the controller does not have sufficient

 

 

power or has failed.

 

 

Unit wiring.

The wiring between the controller outputs and the compressor contacts must be

present and correct for normal compressor operation.

 

 

 

Table 15: Outdoor air damper stays open

Probable Cause

Explanation

 

 

 

The controller opens and closes the outdoor air damper based on the controller’s

Normal operation.

occupancy mode and fan status. Normally, the outdoor air damper is open

during occupied mode when the fan is running and closed during unoccupied

 

 

mode. Refer to the outdoor air damper section on page 8.

 

 

 

The controller includes a manual output test sequence that may be used to verify

Manual output test.

output operation and associated output wiring. However, based on the current

step in the test sequence, the outdoor air damper may not open. Refer to the

 

 

manual output overrides on page 9.

 

 

 

The controller must be properly configured based on the actual installed end

Unit configuration.

devices and application. When the unit configuration does not match the actual

 

end device, the outdoor air damper may not work correctly.

 

 

Unit wiring.

The wiring between the controller outputs and the compressor contacts must be

present and correct for normal damper operation.

 

 

 