Unit Operation

Low Temperature Detection The low temperature detection diagnostic protects the heat exchanger by using an analog leaving water temperature sensor to protect refrigerant circuit 1 and a binary low temperature detection device to protect refrigerant circuit

2.Each individual refrigerant circuit is disabled when the low

temperature condition exists for that circuit.

For two compressor units, the controller responds to low temperature detection by allowing the fan to operate, while disabling the compressor for the faulty circuit. The compressor for the normal circuit continues to operate. The

outdoor air damper also operates normally.

All unit operation is disabled when the heat pump shuts down both circuits, due to low temperature conditions. See Table 3 for more information.

Table 3: ZN510 response to low temperature detection diagnostic

Description

Fan

Compressor Operation

Damper

Operation

Operation

 

 

 

 

Low Temperature Detection

Enabled

Circuit 1-Disabled

Normal

(Circuit 1)

Circuit 2-Normal Operation

operation

 

 

 

 

 

Low Temperature Detection

Enabled

Circuit 1-Normal Operation

Normal

(Circuit 2)

Circuit 2-Disabled

operation

 

 

 

 

 

Low Temperature Detection

Disabled

Circuit 1-Disabled

Closed

(Circuits 1 and 2)

Circuit 2-Disabled

 

 

 

 

 

 

Note:

zThe low temperature detection device automatically resets when the heat exchanger temperature returns to normal. However, you must manually reset the low temperature detection diagnostic to clear the diagnostic and restart the unit. Refer to page 28 on how to reset a unit.

zIf BOP 6 is configured as a generic binary output, the state of the output is not affected by the low temperature detection diagnostic or by other diagnostics.

Condensate Overflow

A condensate overflow switch detects the condensate condition. The condensate overflow switch is a normally closed device. This switch is physically connected to the binary input 2 (BI 2). When the condensation reaches the trip point, the binary input detects the diagnostic condition. A condensate overflow signal generates a diagnostic which disables the fan, disables all compressors, and closes the 2-position outdoor air damper (when present). The condensate overflow diagnostic does not affect the generic binary output (when present).

Note:

The condensate overflow switch, located in the condensate pan, auto- matically resets when the conden- sation returns to normal levels. However, you must manually reset the controller’s condensate over- flow diagnostic to clear the diagnos- tic and restart the unit. Refer to page 28 on how to reset a unit.

Occupancy

ZN510 uses the occupancy binary input for two occupancy-related functions. For standalone controllers (any unit not receiving a communicated occupancy request, typically from a building automation

system), the occupancy binary input determines the unit’s occupancy based on the hardwired signal. Typically, the signal is a dry set of binary contacts which is either connected to a switch or timeclock contacts.

When a hardwired occupancy signal is open, the unit switches to occupied mode (if the occupancy input is configured as normally open). When a hardwired occupancy signal is closed, the controller switches to Unoccupied mode.

10

Page 10
Image 10
Trane Tracer, ZN510 Controller manual Condensate Overflow, Occupancy