Diagnostics

Table 17: ZN510 controller diagnostics

Diagnostic

Fan

Other Outputs

 

 

 

Condensate overflow

Off

Compressors: Off

Damper: Closed

 

 

 

 

 

 

 

Compressor 1: Off

Low temp detect - Crt 1

Enabled

Compressor 2: See note below.

 

 

Damper: See note below.

 

 

 

 

 

Compressor 1: See note below.

Low temp detect - Crt 1

Enabled

Compressor 2: Off

 

 

Damper: See note below.

 

 

 

 

 

Compressor 1: Off

Low temp detect - Crt 1 and 2

Off

Compressor 2: Off

 

 

Damper: Closed

 

 

 

 

 

Compressor 1: Off

High/low press cutout - Crt 1

Enabled

Compressor 2: See note below.

 

 

Damper: See note below.

 

 

 

 

 

Compressor 1: See note below.

High/low press cutout - Crt 2

Enabled

Compressor 2: Off

 

 

Damper: See note below.

 

 

 

 

 

Compressor 1: Off

High/low press cutout - Crt 1 and 2

Off

Compressor 2: Off

 

 

Damper: Closed

 

 

 

Space temperature failure*

Off

Compressor(s): Off

Damper: Closed

 

 

 

 

 

 

 

Compressor 1: Off

Leaving water temp failure

Enabled

Compressor 2: See note below.

Damper: See note below.

 

 

 

 

 

Discharge air temp failure*

Enabled

Compressor(s): No action

Damper: No Action

 

 

 

 

 

Maintenance required

Enabled

Compressor(s): No action

(example: Filter Status)

Damper: No Action

 

 

 

 

Local setpoint failure*

Enabled

Compressor(s): Enabled

Damper: Enabled

 

 

 

 

 

Local fan mode failure*

Enabled

Compressor(s): Enabled

Damper: Enabled

 

 

 

 

 

Invalid unit configuration

Disabled

Compressor(s): Disabled

Damper: Disabled

 

 

 

 

 

High/low pressure cutout and low temperature detection diagnostics for heat pump configurations isolate each circuit and independently disable compressor operation. For single compressor units, these diagnostics cause the compressor to shut down, the unit fan to be controlled off, and the outdoor air damper to be closed (when present).

When BOP 6 is configured as a generic binary output, BOP 6’s state is unaffected by all unit diagnostics.

* Note: Non-latching diagnostics automatically reset when the input is present and valid.

27

Page 27
Image 27
Trane ZN510 Controller, Tracer manual Diagnostics, ZN510 controller diagnostics, Diagnostic Fan Other Outputs