Diagnostics
Table 17: ZN510 controller diagnostics
Diagnostic | Fan | Other Outputs | |
|
|
| |
Condensate overflow | Off | Compressors: Off | |
Damper: Closed | |||
|
| ||
|
|
| |
|
| Compressor 1: Off | |
Low temp detect - Crt 1 | Enabled | Compressor 2: See note below. | |
|
| Damper: See note below. | |
|
|
| |
|
| Compressor 1: See note below. | |
Low temp detect - Crt 1 | Enabled | Compressor 2: Off | |
|
| Damper: See note below. | |
|
|
| |
|
| Compressor 1: Off | |
Low temp detect - Crt 1 and 2 | Off | Compressor 2: Off | |
|
| Damper: Closed | |
|
|
| |
|
| Compressor 1: Off | |
High/low press cutout - Crt 1 | Enabled | Compressor 2: See note below. | |
|
| Damper: See note below. | |
|
|
| |
|
| Compressor 1: See note below. | |
High/low press cutout - Crt 2 | Enabled | Compressor 2: Off | |
|
| Damper: See note below. | |
|
|
| |
|
| Compressor 1: Off | |
High/low press cutout - Crt 1 and 2 | Off | Compressor 2: Off | |
|
| Damper: Closed | |
|
|
| |
Space temperature failure* | Off | Compressor(s): Off | |
Damper: Closed | |||
|
| ||
|
|
| |
|
| Compressor 1: Off | |
Leaving water temp failure | Enabled | Compressor 2: See note below. | |
Damper: See note below. | |||
|
| ||
|
|
| |
Discharge air temp failure* | Enabled | Compressor(s): No action | |
Damper: No Action | |||
|
| ||
|
|
| |
Maintenance required | Enabled | Compressor(s): No action | |
(example: Filter Status) | Damper: No Action | ||
| |||
|
|
| |
Local setpoint failure* | Enabled | Compressor(s): Enabled | |
Damper: Enabled | |||
|
| ||
|
|
| |
Local fan mode failure* | Enabled | Compressor(s): Enabled | |
Damper: Enabled | |||
|
| ||
|
|
| |
Invalid unit configuration | Disabled | Compressor(s): Disabled | |
Damper: Disabled | |||
|
| ||
|
|
|
High/low pressure cutout and low temperature detection diagnostics for heat pump configurations isolate each circuit and independently disable compressor operation. For single compressor units, these diagnostics cause the compressor to shut down, the unit fan to be controlled off, and the outdoor air damper to be closed (when present).
When BOP 6 is configured as a generic binary output, BOP 6’s state is unaffected by all unit diagnostics.
* Note: