period four

Maintenance Considerations

notes

period four

Figure 54

Today, after an absorption chiller is installed and put into operation, it functions without a full-time attendant. In most cases, the chiller starts and stops on a schedule controlled by a building automation system or a simple time clock.

Water chillers are designed for maximum reliability with a minimum amount of maintenance. Like all large mechanical systems, however, certain routine maintenance procedures are recommended. Periodic inspection of the purge system, cooling tower, fluid levels, heat transfer surfaces, energy supply, and pumps helps to maintain the absorption water chiller in peak operating condition. This period discusses these general maintenance requirements of absorption water chillers.

Chilled water inlet and outlet temperatures and pressures

Cooling water inlet and outlet temperatures and pressures

Absorber inlet and outlet solution temperatures and concentrations

Absorber spray solution temperature

Generator inlet and outlet solution temperatures

Evaporator refrigerant temperature

Condenser refrigerant temperature

Crystallization margin

Purge pump-out activity

Gas supply pressure (direct- fired)

Figure 55

Chiller operation should be checked daily and recorded in an operating log. Standard operating logs include: solution data; evaporator, absorber, and

46

TRG-TRC011-EN

Page 51
Image 51
Trane TRG-TRC011-EN manual Maintenance Considerations, Period four