period two

Absorption Chiller Types

notes

low-temperature

 

condenser

 

 

cooling

 

generator

 

water

 

 

 

 

evaporator

chilled

 

 

 

water

 

low-temperature

expansion

 

heat exchanger

 

device

 

 

 

 

absorber

 

 

absorber

evaporator spray pump

 

spray pump

low-temperature

Figure 26

 

 

generator pump

 

 

 

Next, the refrigerant travels through the condenser, expansion device, evaporator and absorber in a manner similar to refrigerant travel in the single- effect absorption chiller.

The low-temperature generator pump returns the dilute absorbent solution to the low-temperature generator to be reconcentrated. This cool dilute solution passes through the low-temperature heat exchanger to be preheated by the hot concentrated solution returning from the two generators.

steam-firedhigh-temperature

high-temperaturegenerator

generatorpump

condensate heat exchanger

high-temperature

 

heat exchanger

Figure 27

 

The high-temperature generator pump draws a portion of the intermediate solution from the low-temperature generator and delivers it to the high- temperature generator to be reconcentrated. Some of this cooler intermediate solution passes through the high-temperature heat exchanger to be preheated by the hot concentrated solution coming from the high-temperature generator. This reduces the heat energy required to boil the refrigerant inside of the high-temperature generator. Precooling the concentrated solution returning

TRG-TRC011-EN

23