period four

Maintenance Considerations

notes

If air leaks into the chiller, the corrosion inhibitor is depleted as it reacts with the

air and produces hydrogen. To maintain chiller efficiency and ensure continued

 

corrosion protection, the lithium bromide solution must be analyzed

 

periodically to determine if corrosion inhibitor and performance additive levels

 

are within acceptable limits. This is the most important periodic maintenance

 

requirement! A laboratory test is required to determine these levels. Suggested

 

intervals for testing are once per year for comfort-cooling applications and

 

twice per year for chillers in continuous or critical service. Analysis of the

 

refrigerant is also recommended. Consult the chiller manufacturer for specific

 

corrosion inhibitor and performance additive recommendations.