period one

Absorption Refrigeration Cycle

notes

dilute

intermediate

concentrated

solution

solution

solution

 

 

Figure 9

These two fluids, the refrigerant and the absorbent, are mixed inside the chiller in various concentrations. The term dilute solution refers to a mixture that has a relatively high refrigerant content and low absorbent content. A concentrated solution has a relatively low refrigerant content and high absorbent content. An intermediate solution is a mixture of dilute and concentrated solutions.

steam or

condenser

hot water

cooling

generator

 

 

water

 

 

evaporator

chilled water

heat exchanger

absorber

Figure 10

Components of the Absorption Cycle

The four basic components of the absorption refrigeration cycle are the generator and condenser on the high-pressure side, and the evaporator and absorber on the low-pressure side. The pressure on the high-pressure side of the system is approximately ten times greater than that on the low-pressure side.

8

TRG-TRC011-EN

Page 13
Image 13