Trane UX1D120A9601A, UX1C100A9481A Installer’s Guide, Horizontal Applications, Upflow Vertical

Models: UX1D100A9601A DX1B060A9361A UX1D120A9601A DX1B080A9421A DX1B040A9241A DX1C100A9481A DX1D120A9601A UX1B040A9241A UX1B060A9241A UX1B060A9361A UX1B080A9241A UX1B080A9421A UX1C100A9361A UX1C080A9601A UX1C100A9481A

1 40
Download 40 pages 62.41 Kb
Page 27
Image 27
HORIZONTAL APPLICATIONS

HORIZONTAL APPLICATIONS

Upflow and Downflow furnaces - All horizontal ap- plications are left side only. It is always recommended that the auxiliary drain pan be installed under a hori- zontally installed evaporator and/or 90% gas furnace. Connect the auxiliary drain pan to a separate drain line (no trap is needed in this line).

&

Left side

UPFLOW (VERTICAL)

*

Use

extension hose here

UPFLOW HORIZONTAL 21" & 24" UNITS

(Left side only)

The trap must be repositioned to the exterior of the cabinet. Remove the trap from its present location and reposition the trap outside of the unit, through the long circular hole, next to the secondary recuperated cell. Remove the larger drain line (from the secondary cell) and trim to fit between the secondary cell and the new trap location. On upflow units, plug the hole in the blower deck where the tube went through.

Remove the hose from the induced blower and reposi- tion into the other drain tap of the inducer, which is lo- cated 90° clockwise around the inducer. Move the cap from that drain tap to the unused drain tap. On upflow units, plug the hole in the blower deck where the tube went through. This tube on downflow units will need to be cut to fit between the inducer and the trap. On upflow units, this tube may need to be extended, using the tubing shipped with the furnace.

Installer’s Guide

(

Left side

DOWNFLOW (VERTICAL)

)

UPFLOW HORIZONTAL 21" & 24" UNITS Right side

Use CPVC tubing from Trap outlet,

over burner box to cabinet exit

DOWNFLOW (VERTICAL)

Q

Cut off curved end of

Inducer drain hose

DOWNFLOW (HORIZONTAL)

Connections must be made to an OPEN/ VENTED DRAIN. Outdoor draining of the furnace and coil con- densate is permissible if allowed by local codes. Caution should be taken to prevent drains from freezing or caus- ing slippery conditions that could lead to personal in- jury. Excessive draining of condensate may cause satu- rated ground conditions that may result in damage to plants.

18-CD19D6-32

27

Page 27
Image 27
Trane UX1D120A9601A Installer’s Guide, Horizontal Applications, Upflow Vertical, Downflow Vertical, Downflow Horizontal