HIGH ALTITUDE DERATE

Installer’s Guide

HIGH ALTITUDE DERATE

Input ratings (BTUH) of these furnaces are based on sea level operation and should not be changed at eleva- tions up to 2,000 ft.

If the installation is 2,000 ft. or above, the furnace input rate (BTUH) shall be reduced 4% for each 1,000 ft. above sea level. The furnace input rate shall be checked by clocking the gas flow rate (CFH) and multiplying by the heating value obtained from the local utility sup- plier for the gas being delivered at the installed altitude. Input rate changes can be made by adjusting the mani- fold pressure (min 3.0 - max 3.7 in. W.C. - Natural Gas) or changing orifices (orifice change may not always be required). If the desired input rate can not be achieved with a change in manifold pressure, then the orifices must be changed. LP installations will require an orifice change.

Installation of this furnace at altitudes above 2,000 ft. (610m) shall be in accordance with the local codes, or in the absence of local codes, the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 or National Standard of Canada, Natural Gas and Propane Installation Code, CSA 149.1. Installation of this furnace at altitudes above 2,000 ft. (610m) shall be made in accordance with the listed high Altitude Conversion Kit available with this furnace.

IMPORTANT:

Re-install the propane orifices to the same depth as the orifices supplied with the equipment.

U

ROTATE THE FRONT

 

COVER AS SHOWN

 

INSERT THE TOP

 

FLANGE OF THE FRONT

 

COVER UNDER THE LIP

 

INSIDE THE BOX

 

ALL SIDE FLANGES

 

MUST BE OUTSIDE OF

 

THE BOX

 

ROTATE THE FRONT

 

COVER INWARD

 

MAKING SURE THAT

 

ALL SIDE FLANGES

 

ARE OUTSIDE OF THE

 

BOX.

TABLE 16

GAS FLOW IN CUBIC FEET PER HOUR

2 CUBIC FOOT DIAL

SEC.

FLOW

SEC.

FLOW

SEC.

FLOW

SEC.

FLOW

8

900

29

248

50

144

82

88

9

800

30

240

51

141

84

86

10

720

31

232

52

138

86

84

11

655

32

225

53

136

88

82

12

600

33

218

54

133

90

80

13

555

34

212

55

131

92

78

14

514

35

206

56

129

94

76

15

480

36

200

57

126

96

75

16

450

37

195

58

124

98

73

17

424

38

189

59

122

100

72

18

400

39

185

60

120

104

69

19

379

40

180

62

116

108

67

20

360

41

176

64

112

112

64

21

343

42

172

66

109

116

62

22

327

43

167

68

106

120

60

23

313

44

164

70

103

124

58

24

300

45

160

72

100

128

56

25

288

46

157

74

97

132

54

26

277

47

153

76

95

136

53

27

267

48

150

78

92

140

51

28

257

49

147

80

90

144

50

34

18-CD19D6-32

Page 34
Image 34
Trane UX1B080A9241A, UX1C100A9481A, UX1C080A9601A, UX1C100A9361A, UX1B080A9421A manual Installer’s Guide, High Altitude Derate