Trane DX1D120A9601A manual Installer’s Guide, Air For Combustion And Ventilation, Unconfined

Models: UX1D100A9601A DX1B060A9361A UX1D120A9601A DX1B080A9421A DX1B040A9241A DX1C100A9481A DX1D120A9601A UX1B040A9241A UX1B060A9241A UX1B060A9361A UX1B080A9241A UX1B080A9421A UX1C100A9361A UX1C080A9601A UX1C100A9481A

1 40
Download 40 pages 62.41 Kb
Page 8
Image 8
UNCONFINED

Installer’s Guide

5

UPFLOW/

HORIZONTAL

SHOWN

The furnace may be placed horizontally in a crawl space on a pad or other noncombustible material which will raise the unit for sufficient protection from moisture.

The furnace must be supported at both ends and the middle when installed horizontally.

The furnace must also be elevated a minimum of 6 inches to allow clearance for the condensate drain to exit the cabinet in the horizontal position.

The horizontal furnace may also be suspended from the joists using 3/8" all-thread rods with pieces of angle iron underneath the furnace to form a hanging rack at both ends and the midpoint. The rods need to be of sufficient length to allow for proper clearances from combustible materials. The angle iron needs to be at least 32" in length to allow for access to service panels.

6

50 CU. FT. OR MORE PER 1000 BTU/HR. INPUT ALL EQUIP. INSTALLED

UNCONFINED

AIR FOR COMBUSTION AND VENTILATION

If these furnaces are installed in a nondirect vent capac- ity then the adequate flow of combustion and ventilat- ing air must not be obstructed from reaching the fur- nace. Air openings provided for combustion air must be kept free of obstructions which restrict the flow of air. Airflow restrictions affect the efficiency and safe opera- tion of the furnace. Keep this in mind should you choose to remodel or change the area which contains your furnace. Furnaces must have a free flow of air for proper performance.

Provisions for combustion and ventilation air shall be made in accordance with latest edition of Section 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1 — CAN/CGA B149.1 or ap- plicable provisions of the local building codes. Special conditions created by mechanical exhausting of air and fireplaces must be considered to avoid unsatisfactory furnace operation.

OUTSIDE AIR IS RECOMMENDED

The use of indoor air for most applications is acceptable, unless there is the presence of corrosive chemicals or contamination. Certain types of installation will require the use of outside air for combustion.

The following types of installations will require use of OUTDOOR AIR for combustion, due to chemical expo- sures:

*Commercial buildings

*Buildings with indoor pools

*Furnaces installed in “confined” laundry rooms

*Furnaces installed in “confined” hobby or craft rooms

*Furnaces installed near chemical storage areas. Exposure to the following substances in the combustion air supply will also require OUTDOOR AIR for combus- tion:

*Permanent wave solutions

*Chlorinated waxes and cleaners

*Chlorine based swimming pool chemicals

*Water softening chemicals

*Deicing salts or chemicals

*Carbon Tetrachloride

*Halogen type refrigerants

*Cleaning solvents (such as perchloroethylene)

*Printing inks, paint removers, varnish, etc.

*Hydrochloric acid

*Cements and glues

*Antistatic fabric softeners for clothes dryers

*Masonry acid washing materials

Furnace locations may be in a “confined space” or an “unconfined space”.

Unconfined space is defined in Figure 6. These spaces may have adequate air by infiltration to provide air for combustion and ventilation. Buildings with tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), may need addi- tional air to be provided as described for confined space. Confined spaces are installations with less than 50 cu. ft. of space per 1000 BTU/hr input from all equipment installed. Air for combustion and ventilation require- ments can be supplied from inside the building as in Figure 8 or from the outdoors, as in Figure 9.

8

18-CD19D6-32

Page 8
Image 8
Trane DX1D120A9601A manual Installer’s Guide, Air For Combustion And Ventilation, Unconfined, Outside Air Is Recommended