Vanguard Heating VS30PR Air For, Combustion, Ventilation Air From Outdoors, Continued

Models: VS18PR VS30PR VS24PR

1 32
Download 32 pages 41.47 Kb
Page 7
Image 7
AIR FOR

AIR FOR

WARNING

COMBUSTION

If the area in which the heater may be operated is smaller than that defined as an uncon-

AND

fined space, provide adequate combustion and ventilation air by one of the methods

VENTILATION

described in the National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

 

 

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining uncon- fined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

COMBUSTION WARNING

Rework worksheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

 

 

12"

Ventilation

 

Ventilation Grills

Grills

 

Into Adjoining

Or

Into Adjoining Room,

Room,

Option 2

Remove

Option 1

 

Door into

 

 

 

 

Adjoining

 

 

Room,

 

 

Option

 

 

3

 

 

 

12"

Figure 2 - Ventilation Air from Inside Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

7

103448

Page 7
Image 7
Vanguard Heating VS30PR Air For, Combustion, Ventilation Air From Inside Building, Ventilation Air From Outdoors