Venting System Assembly

General Information

The Stardance is approved for installation only with the vent components listed on Pages 12 & 13. Follow the vent component instructions exactly.

For U.S. installations: The venting system must con- form with local codes and/or the current National Fuel Gas Code, ANSI Z223.1/NFPA 54

For Canadian installations: The venting system must conform to the current CSA B149.1 installation code.

Rear Vent

Use Rear Vent Kit 7TFSRSK for an installation where the heater is parallel to the wall and the vent system extends straight back through that wall.

1.Attach Inner Starter Pipe, (found in with the logset), to the stove.

Run a bead of sealant beneath the pipe bead and attach to the stove using three 1/4-20 x 3/8” phillips screws provided in the parts bag. (Fig. 17)

Stardance Direct Vent - Rear Vent Gas Heaters

2.Locate the vent opening on the wall. Refer to Fig- ures 18 & 19 to determine the top of the opening centerline. It may be necessary to first position the stove and measure to find the hole location. De- pending on whether the wall is made of combustible materials, cut the opening to the size shown in Fig- ure 18. Combustible wall openings must be framed as shown in Figure 18.

Vent Opening - Combustible Wall

9³⁄"

(240mm)

9³⁄"

(240mm)

Framing Detail

Vent Opening -Noncombustible Wall

7¹⁄"

(191mm)

VO584-100

Fig. 18 Locate vent opening.

3.Measure the wall thickness and cut the wall sleeve sections to proper length (MAXIMUM 12”). Assemble the sleeve with the #8 sheet metal screws supplied. Attach the firestop plate to the sleeve end with the holes. (Fig. 24) NOTE: The wall sleeve is required in combustible walls only.

4.Install the Wall Firestop/Sleeve assembly into the wall cutout and fasten the firestop to the wall cutout framing members. (Figs. 19)

5.Measure, and cut if necessary, the appropriate length of pipe section needed to make the connec- tion through the wall.

Sealant

Phillips

Screws

ST937

Fig. 17 Apply sealant to the starter pipe, and fasten to stove with Phillips screws.

9³⁄” W x 10³⁄” H Wall Opening

Wall Sleeve

- Seal Around

 

C

 

L

 

27���"

 

(695mm)

 

to Top of

Seal

Opening

Around

22���

(565 mm)

Terminal

 

ST477

Firestop

Ventilated Wall Plate

-Open End Down Finishing Collar

Fig. 19 Rear Vent Kit 7TFSRSK installation.

20012950

15