Verona WALL HUNG GAS BOILER manual Commissioning Cont, 15.3Checking the gas pressure at the burner

Models: WALL HUNG GAS BOILER

1 40
Download 40 pages 26.81 Kb
Page 31
Image 31
15.Commissioning Cont.

15.Commissioning Cont.

15.3Checking the gas pressure at the burner:

This boiler has been tested to the highest quality control standards.

The maximum and minimum gas pressures are already set during this quality control process however the checking procedure must be followed to ensure maximum operating efficiency from the boiler.

Remove the front

 

fitted (e.g. room

removing the electrical

 

 

panel of the case.

 

thermostat) ensure

connector E (Figure

Loosen the internal

 

they "call for heat".

15.4).

 

 

screw 15 (Figure

Switch on the boiler.

• Switch on the boiler.

 

 

15.4) on the Outlet

Check the maximum

• Check the minimum

 

 

Pressure Test Point

 

gas pressure and

gas pressure and

 

 

of the Gas Valve and

 

compare the value on

compare the value on

 

 

connect a pressure

 

the gauge with the

the gauge with the

 

 

gauge using a

 

value indicated in the

value indicated in the

 

 

suitable hose.

 

Section 2 on page 10

Section 2 on page 10

 

 

 

 

 

 

 

 

(gas pressures at the

(gas pressures at the

 

 

 

 

 

 

 

 

burner).

burner).

 

 

15

 

 

 

 

 

 

 

 

 

 

 

Check the maximum

• Switch off the boiler

 

 

 

 

 

 

 

 

 

16

 

 

E

 

 

gas flow at the gas

and re-connect the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

meter and compare

electrical connector E

 

 

 

 

 

 

 

 

the value indicated in

to the modulator coil.

 

 

 

 

 

 

 

 

the section 2 on page

• Switch on the boiler.

 

 

 

 

 

 

 

 

10 (gas flow rate).

• Check that the boiler

 

 

 

Figure 15.4

• Switch off the boiler.

lights up uniformly.

 

 

 

Disconnect the gas

• Switch off the boiler,

Set the

c.h.

 

modulator coil by

turn off the hot water

 

 

temperature control

 

 

taps and disconnect

 

 

knob to its maximum

 

 

the pressure gauge.

 

 

position. If external

 

 

Important: after the

 

 

controls are

 

 

checks all of the test

points must be sealed.

RIVA HEAT ONLY MANUAL - REV A

31

Page 31