INSTRUCTIONS MANUAL

If the high and low gauges indicate positive pressure, then recover the refrigerant in the hoses back into the storage tank.

1.Disconnect the machine from main power supply.

2.Put on gloves and safetygoggles.

3.Remove the rear plastic cover.

4.Close the valves on the storage tank.

5.Close the L.P. filter-tap. (3)

6.Working slowlyand carefully, unscrew the couplings at the inlet and outlet to the filters.

7.Loosen the filter clamps.

8.Replace the filters, taking care to insert them in the correct direction. (1,2)

9.Tighten the clamps and the couplings at the inlet and outlet to the filters.

10.Open the valves on the storage tank.

11.Open the L.P. filter-tap. (3)

12.Replace the rear plastic cover.

13.Reconnect and switch on the MACHINE.

14.During the first 10 seconds (when the service alarm [SERV] is displayed), press the SEL key.

15.Type in the filter code 0014 to cancel the alarm (use the INCREASE and ARROW keys).

16.Charge and recover about 8 oz. of refrigerant to charge the machine circuit.

17.Switch off the MACHINE

18.Disconnect the machine from main power supply.

CAUTION: Replace the old filter with the new one as quickly as possible in order to avoid possible contamination with the humidity in the ambient air.

EMPTYING THE USED OIL TANK

This operation must be performed after every recovery.

Procedure: remove the tank from its lodging and unscrew the cap; empty the tank into a container for used oils, Replace the cap and replace the container in its lodging.

CASE CARE

If the case of the unit becomes soiled, clean with a mild detergent and a clean rag. Do not use solvents – some solvents maycause a deterioration of the material and harm your A/C Service Center.

AIR CONDITIONING HOSE MAINTENANCE

The manufacturer recommends that the hose seals be checked periodically and replaced at the beginning of each season, at minimum. Contact your local distributor when replacement seals are needed.

CALIBRATING THE ELECTRONIC SCALE

This operation should be performed when the scale values displayed are out of line with known values. The operations listed below must be performed with the maximum attention and care. Always observe the precautions outlined in this section. Always place the weights carefully on the scale plate, one at a time. Always place the weights the center of the scale plate. Proceed as explained below to calibrate the scale (see fig. 1, 2, 3, & 4). Disconnect the machine from main power supply. Procure a known reference weight (50 lbs). Remove the plastic cover on the rear of the machine to access the machine bottle. Close the blue and red valves on the storage tank. Remove the storage tank locking bolts. Separate the heater

21

Page 21
Image 21
Viper VR-6000 Emptying the Used OIL Tank, Case Care, AIR Conditioning Hose Maintenance, Calibrating the Electronic Scale

VR-6000 specifications

The Viper VR-6000 is an innovative addition to the realm of virtual reality headset technology, designed to offer users an immersive and visually stunning experience. Built with meticulous attention to detail, the VR-6000 provides an ideal mix of high-end performance, comfort, and cutting-edge features that cater to both gamers and tech enthusiasts alike.

One of the standout characteristics of the Viper VR-6000 is its high-resolution display. The headset boasts a dual 4K OLED screen that delivers an exceptional pixel density, resulting in incredibly sharp visuals and vibrant colors that breathe life into the virtual environments. This feature significantly enhances the sense of realism, making every gaming session or virtual experience captivating.

The VR-6000 is powered by advanced refresh rate technology, providing a refresh rate of up to 120 Hz. This ensures smooth and fluid visuals, minimizing motion blur and enhancing responsiveness during fast-paced action scenes. Coupled with low-latency tracking, players can enjoy an almost instantaneous response as they move within their virtual space, making the experience feel more natural and engaging.

Comfort is another focal point of the Viper VR-6000 design. The headset has a lightweight frame and adjustable padding, which accommodates prolonged use without discomfort. It is designed to fit a wide range of head sizes, with a customizable strap system ensuring a secure and snug fit. Additionally, the integrated audio system features spatial sound technology that offers 3D audio experiences, allowing users to hear sounds from all directions, further enhancing immersion.

On the technological front, the Viper VR-6000 comes equipped with advanced motion tracking sensors. Utilizing a combination of inside-out tracking and external base stations, it allows for precise movement detection, which is crucial for room-scale VR experiences. Users can move freely within their designated space, and the system accurately reflects these movements in real time.

Compatibility is another highlight of the VR-6000. It supports a wide range of platforms, including both PC and console, allowing users to access an extensive library of VR titles. Moreover, the headset includes easy-to-use connectivity options, such as wireless capability and USB-C support, ensuring seamless integration with various devices.

In summary, the Viper VR-6000 represents a significant leap in virtual reality technology, offering an impressive array of features and capabilities. With its high-resolution display, advanced motion tracking, exceptional comfort, and compatibility with multiple platforms, it stands out as a top choice for those seeking an immersive VR experience. Whether for gaming, simulations, or interactive media, the VR-6000 promises to elevate the way users engage with the virtual world.