Viper VR-6000 owner manual C1 C2 C3 C4, Status And Alarm Panel

Models: VR-6000

1 76
Download 76 pages 26.06 Kb
Page 12
Image 12
STATUS AND ALARM PANEL

INSTRUCTIONS MANUAL

or Fahrenheit degree.

(T13) Display: According to the operation selected, displays the evacuation time, tank temperature, or weight of available refrigerant.

STATUS AND ALARM PANEL

See Fig 7:

(C1) REPLACE FILTER: the Low side refrigerant filter/dryer must be changed when the led “REPLACE FILTER” lights up. When recovering new refrigerant this light may come on prematurely. It maybe reset bypressing the SEL keywhile turning on the machine.

(C2) HIGH PRESSURE: Lights and emits an acoustic signal when the pressure of the fluid in the circuit exceeds 290 psi (20 bar). The RECOVERY operation is automatically interrupted. This will occur if you attempt to recover refrigerant with the tank valves closed, and will require some disassembly to reset (see TROUBLE SHOOTING section)

(C3) TANK FULL: Lights and emits an acoustic signal when the bottle is filled to more than 80% of maximum capacity, approximately 40 lbs. The RECOVERY operation is automatically interrupted. You may use the CHARGING function to remove refrigerant from the storage tank.

(C4) LOW REFRIGERANT: Lights and emits an acoustic signal when the quantity of refrigerant fluid contained in the bottle is low, near 4 lbs (~2 kg). You will need to add additional refrigerant to continue with a CHARGING function.