FAQs

1F95-391

 

 

(cont. )

is dependent on system sizing, thermostat location, etc. Note: The thermostat display only

13.Why does the system run

displays whole numbers. Internally the thermostat calculates decimals.

with the setpoint and room

In heating as the room temperature increases the system will continue to run until the

temperature the same?

thermostat reaches the high side of the temperature setpoint.

 

 

 

14. How do I reset my

There are 3 possibilities to consider, excluding tampering.

thermostat?

1. Loss of power from the system, 24VAC should be constant to maintain a display.

 

 

2. Static electricity or a voltage spike from the heating equipment might be resetting the

 

thermostat. Static electricity can be eliminated by touching something before touching the

 

thermostat to dissipate the static charge. A voltage spike from the equipment can be

 

eliminated using an isolation relay as described in the link below.

 

http:www.white-rodgers.com/pdfs/instruction_sheets/0037_5426_A.pdf

 

You can also check the wire routing to verify the thermostat or remote wires are not running

 

parallel to high voltage lines with high inductive loads which could (in extreme cases)

 

create a voltage spike at the thermostat.

 

3. Thermostat not functioning properly. A simple test would be to bench test one of the units

 

for a couple of days to see if it resets or move it to another system where a reset has never

 

occurred.

 

 