Troubleshootin g

SYMPTOM

POSSIBLE CAUSE

CORRECTIVE ACTION

 

 

 

Heat, Cool or Fan Runs

1. Possible short in wiring.

Check each wire connection to verify they are not

Constantly

 

shorted or touching together. No bare wire should

 

 

stick out from under terminal screws.

 

2. Possible short in thermostat.

Try resetting the thermostat as described on page 31.

3.Possible short in heat/cool/fan system.

4. Fan Switch is set to Fan On.

If the FAN button is pressed to display ON, the

 

blower fan will cycle continuously whether the

 

heating or cooling system is running, press the FAN

 

button until AUTO is displayed. If the condition

 

persists, the manufacturer of your system or service

 

person can instruct you on how to test the Heat/Cool

 

system for correct operation. If the system operates

 

correctly, replace the thermostat.