Freedom Inverter/Charger Configuration

Setting Battery Types on the Main Unit

You can attach different types of lead-acid batteries to the Freedom HF. Before installing batteries make sure that you configure the unit to optimize the charging process.

The settings can be changed by adjusting the dip switches found on the main unit behind the display panel.

Battery

Dip Switch

Bulk/

Float

Type

Setting

Absorption

 

 

Switch 1Switch 2

 

 

Fixed

OFFOFF

13.5

13.5

 

 

 

 

Flooded

OFFON (default)

14.4

13.5

 

 

 

 

GEL

ONOFF

14.2

13.8

 

 

 

 

AGM

ONON

14.3

13.4

 

 

 

 

To adjust the battery type setting:

By default the battery type is set to Flooded (OFFON).

1.Detach the Display Panel to expose the Dip Switches.

2.Use the tip of your fingernail or a small screw driver with a flat tip to adjust the switches.

OFF

ON

Switch 1 Switch 2

Figure 2 Dip Switches (Default Settings Shown)

975-0390-01-01

9

Page 23
Image 23
Xantrex Technology 806-1054-01, 806-1840 Freedom Inverter/Charger Configuration, Setting Battery Types on the Main Unit