Installation
Installing the Mounting Bracket
The mounting bracket for the GT Inverter allows the unit to be easily mounted and removed for servicing. It has one hook that matches a corresponding hook on the back side of the inverter.
Mounting flanges
23.8 cm 9.4"
18.3cm
7.2"
Rectangular slots × 8:
8 mm × 30 mm (5/16" ×
Mounting slots for securing the inverter
Figure
Clearance Requirements
For optimal and safe operation, ensure there is adequate clearance around the inverter. The minimum clearance recommendations in Table
Table
Location | Minimum Clearance | |
|
| |
Above | 30 cm (12 inches) | |
Below: | Outdoors: | |
• | Inverter | • 100 cm (39 inches) |
• | Bracket | • 130 cm (51 inches) |
|
| Indoors: the same clearances are recommended but not required. |
In front | Sufficient room to allow for easy access to read the display and to prevent | |
|
| accidental contact with hot surface. |
On sides | Units can be mounted side by side with no clearance between them, but | |
|
| 15 cm (6 inches) of clearance around the outermost two units is |
|
| recommended. In hot climates, some clearance between units may be |
|
| needed to prevent thermal derating. |
|
|
|