Installation

Installing the Mounting Bracket

The mounting bracket for the GT Inverter allows the unit to be easily mounted and removed for servicing. It has one hook that matches a corresponding hook on the back side of the inverter.

Mounting flanges

23.8 cm 9.4"

18.3cm

7.2"

Rectangular slots × 8:

8 mm × 30 mm (5/16" × 1-3/16")

Mounting slots for securing the inverter

Figure 2-5Mounting Bracket and GT Inverter

Clearance Requirements

For optimal and safe operation, ensure there is adequate clearance around the inverter. The minimum clearance recommendations in Table 2-2assume a vertical mounting. If clearances are less than these recommendations are used, additional power reduction may occur at high ambient temperatures.

Table 2-2Inverter Clearance Requirements

Location

Minimum Clearance

 

 

Above

30 cm (12 inches)

Below:

Outdoors:

Inverter

• 100 cm (39 inches)

Bracket

• 130 cm (51 inches)

 

 

Indoors: the same clearances are recommended but not required.

In front

Sufficient room to allow for easy access to read the display and to prevent

 

 

accidental contact with hot surface.

On sides

Units can be mounted side by side with no clearance between them, but

 

 

15 cm (6 inches) of clearance around the outermost two units is

 

 

recommended. In hot climates, some clearance between units may be

 

 

needed to prevent thermal derating.

 

 

 