Connecting the DC Wiring
•Female and male DC cable connectors to mate with the
The following procedure is illustrated in Figure
1.If necessary, install DC conduit from the PV string(s) to the GT Inverter.
2.Terminate the wires coming from the PV string(s) with appropriate
CAUTION: Equipment damage
Before connecting the PV array to the inverter, check to ensure correct polarity and that the voltage between the positive (+) and negative
To check the PV array DC voltage:
1.Uncover the PV arrays and expose them to full sunlight. The sunlight must be intense enough to produce the required output voltage.
2.Measure the PV array open circuit DC voltage across the DC positive (+) and negative
3.Cover the PV arrays with an opaque material again.
3.Connect the POSITIVE (+) wire from the #1 PV string to a GT Inverter PV positive (+) quick connect.
4.Connect the NEGATIVE
5.If necessary, repeat for the #2 PV string. Double check that the wires are in the proper locations.
If only one PV string connection is used, cover the unused PV quick connects with the seals provided.
WARNING: Shock hazard
Never connect or disconnect the PV modules from the GT Inverter under load (by pulling the PV quick connects before disconnecting the grid). Always disconnect the GT Inverter from the grid first.