About Link 1000 Settings
F05 Turn on Alternative Energy Mode
Default: Off
Range: Off and On. On = use alternative energy defaults.
Turn Alternative Energy mode on if the Link 1000 is used in an alternative energy system.
This function reduces the time needed to satisfy the charged parameters from five minutes to one minute. If you are using a
F06 Manually Set CEF
Default: Off = Auto recalculation of CEF
Display: A95
Range:
This setting allows manual set up of CEF (Charging Efficiency Factor). The default display A95 indicates the automatic CEF recalculation feature. Returning to A95 from a
F07 Set Temperature Coefficient
Default: 0.5
Range:
We recommend that you use the default value.
This factor compensates for the impact that temperature has on battery capacity. A typical value is 0.5% Capacity per °C. This coefficient must be supplied by the battery manufacturer. The default value is typical for liquid