Reading Error Codes
Reading Error Codes
When the Link 1000 detects a problem, an error code appears in the numeric display. The display alternates between showing the monitoring function you have selected and the error code. The error code flashes until the error is corrected.
The following table lists each Error Code, describes the cause of the error, and indicates the action to take, if any.
Error |
|
Code | Meaning |
|
|
E01 | High battery voltage shutdown |
| (Inverter/charger error) |
| Battery voltage has risen above 15.5 V for 12 V |
| inverters or above 31 V for 24 V inverters. |
| Check all charging sources (that is, solar panels, |
| alternators, etc. |
E02 | Low battery voltage shutdown |
| (Inverter/charger error) |
| Battery voltage has dropped below 10.5 V for 12 V |
| inverters or below 21 V for 24 V inverters. |
| Check for a dead battery or poor battery connections. |
E03 | Over temperature shutdown |
| (Inverter/charger error) |
| The inverter has overheated and shut down. It will reset |
| automatically after it has cooled sufficiently. |
| Make sure there is adequate ventilation around the |
| inverter. |
E04 | Battery overload |
| (Inverter/charger error) |
| The battery is excessively discharged or there is a |
| shorted battery. |
| See your inverter/charger owner’s manual for |
| information about charging excessively discharged |
| batteries. |
|
|
48