Extended Length Installations

2.0 INSTALLATION

Extended Length Installations

If the TM500A is mounted in excess of 100 feet from the inverter, an

additional wire (with a spade lugs on both ends) must be connected between the TM500A and shunt spade lugs. This wire acts as a ground reference and ensures the meter will read accurately.

Use the following gauge wire for the distance the TM500A is mounted from the inverter.

Maximum Distance

Wire Gauge

250

feet

#16 AWG

400

feet

#14 AWG

630

feet

#12 AWG

1000 feet

#10 AWG

J2 TO

 

INVERTER

J1 TO

ONLY

SHUNT

 

ONLY

 

SPADE LUG

Interconnect for distances over

100 feet

SPADE LUG

Figure 2-6

Extended Length Ground Wire