Trigger on Voltage and Time

3.0 CONFIGURATION

Setting Parameters (continued)

CHARGED Indicator Setup Manual background (continued)

Trigger on Voltage and Time

When this mode is selected, the CHARGED indicator LED illuminates when the voltage reaches the programmed level (Step A) and the amperage remains positive for the specified time (Step B).

Step A Setting the Fully-Charged Voltage Level

1A. Press the SELECT button until the Voltage LED ( V ) is illuminated.

2A. Press the SELECT and RESET buttons simulataniously until the LED display flashes.

3A. Press the RESET button to change the displayed voltage to the desired fully charged voltage level.

For a 12 VDC system, set this voltage between 14.3–14.9 volts for lead-acid batteries.

For a 24 VDC system, set this voltage between 28.6–29.6 volts for lead-acid batteries.

For a 48 VDC system, set this voltage between 57.2–59.2 volts for lead-acid batteries.

Refer to the battery manufacturer’s recommendation for other types of batteries.

4A. Press the SELECT button to accept the new value. The selection range is between 10 to 64.9 VDC.

5A. Proceed to Step B.

 

Set Voltage Level

 

14.4

 

Voltage LED Illuminates

1A

to Indicate the Voltage

Function is Selected

4A

2A

3A

Figure 3-9

Setting the CHARGED Indicator Voltage Level