3.0 CONFIGURATION
Setting Parameters (continued)
CHARGED Indicator Setup (continued)
Trigger on Voltage and Time
When this mode is selected, the CHARGED indicator LED illuminates when the voltage reaches the programmed level (Step A) and the amperage remains positive for the specified time (Step B).
Step A Setting the
1A. Press the SELECT button until the Voltage LED ( V ) is illuminated.
2A. Press the SELECT and RESET buttons simulataniously until the LED display flashes.
3A. Press the RESET button to change the displayed voltage to the desired fully charged voltage level.
•For a 12 VDC system, set this voltage between
•For a 24 VDC system, set this voltage between
•For a 48 VDC system, set this voltage between
Refer to the battery manufacturer’s recommendation for other types of batteries.
4A. Press the SELECT button to accept the new value. The selection range is between 10 to 64.9 VDC.
5A. Proceed to Step B.
| Set Voltage Level |
| 14.4 |
| Voltage LED Illuminates |
1A | to Indicate the Voltage |
Function is Selected |
4A
2A | 3A |
Figure
Setting the CHARGED Indicator Voltage Level