Step B Setting the Amperage Trigger Level

3.0 CONFIGURATION

Setting Parameters (continued)

CHARGED Indicator Setup Trigger on Voltage and Amperage (continued)

Set Voltage Level

14.4

Voltage LED

Illuminates to Indicate

1Athe Voltage Function is Selected

4A

2A

3A

Figure 3-7

Setting the CHARGED Indicator Voltage Level

Step B Setting the Amperage Trigger Level

1B. Press the SELECT button until the Amperage LED ( A ) is illuminated.

2B. Press the SELECT and RESET buttons simulataniously until the LED display flashes.

3B. Press the RESET button until the display indicates the desired amperage.

4B. Press SELECT button to accept.

The selectable amperage values are from 1 to 99 amps.

The TM500A is now setup to trigger the CHARGED indicator LED (Manual backgroundManual backgroundManual backgroundManual backgroundManual background) when the voltage level equals or exceeds the value programmed in Step A and the amperage level falls below the value programmed in Step B. When these parameters are met, the CHARGED indicator LED flashes approximately every four seconds. Whenever the current goes negative (discharge) the timer resets to zero. The CHARGED indicator must be manually reset to turn it OFF.

 

 

Set Amperage

1B

44A

Amperage LED

Illuminates to Indicate the

 

 

Amperage Function is

4B

 

 

2B

3B

Figure 3-8

Trigger on Voltage and Amperage

20

© 2001 Xantrex Technology Inc.

P/N 973-0012-01-02 Rev.A05/01