5.0 TROUBLESHOOTING
Symptom | Possible Cause | Solution |
LED in INVERTER ON/OFF | J2 plug not plugged into | Plug cable into TM500A and |
switch does not light. | TM500A or the inverter. | Inverter's RC4/RC8 remote |
|
| control jack. |
| Inverter does not have a | The inverter remote control |
| compatable Jack. | only operates on models |
|
| equipped with an RC4/RC8 |
|
| remote control input. |
|
|
|
Voltage displayed on | The TM500A voltage is | Reconfigure the TM500A for |
meters is not correct. | configured above 35.0 volts | the correct system voltage |
| for a 12- or | (see Section 3, |
|
| Configuration, Charged |
| The TM500A voltage is | Indicator |
| configured below 35.0 volts |
|
| for a |
|
|
|
|
Battery | Reconfigure the amp hours to | |
displays "FULL" when |
| the correct setting - Battery |
voltage is low. |
| bank size (see Section 3, |
|
| Configuration, Setting |
|
| Parameters, Amp Hours). |
|
|
|
bLO displays a voltage of | The bLO meter was not | Reconfigure the |
00.0. | configured during | Indicator (bLO) for the correct |
| after being disconnected | |
| from the shunt. | Section 3, Configuration, |
|
| Setting Parameters, Low- |
|
| Voltage Indicator). |
|
|
|
CHARGED LED continues | VOLTAGE ONLY | Reconfigure the CHARGED |
to flash even though the | configuration for the | voltage to an appropriate |
current flow is negative | Charged Indicator Setup | value (i.e., 12.6 V for a |
(battery discharging) | may be set too low. | |
continuously for one minute. |
| 3, Configuration, Setting |
|
| Parameters, Charged |
|
| Indicator Setup). |
|
| The CHARGED indicator |
|
| must be manually reset to turn |
|
| it OFF. |
|
|
|
|
|