direction may be adjusted with the CLOSE SENSITIVITY preset. (Pic 37)
Pic 37
If it is required to increase the obstruction sensitivity, thus reducing the door edge pressure required to activate the control unit obstruction sensing circuit, which causes the door to stop and
Pic 38
Note that this will also increase the possibility of the controller reacting to slight abnormalities or minor damage to the track or misalignment of track sections. This may cause fluctuations in the motor current and may be significant enough to result in the door stopping and
Both preset controls are factory set to the 12
Pic 39
If either of the preset controls is adjusted, the compression of the door edge seal will be affected and thus the position of the fully closed door may be different to the calibrated reference. In which case it may be necessary to complete a new Calibration Reset procedure.
SAFETY CIRCUIT WIRING
If the door is to be operated without any supplementary safety devices then the STANDARD SAFETY SWITCH, DIP switch No. 2 and the 12 volt
If a safety device such as a Standard
If a
Pic 40
14