Chromalox 1604-7 user manual Serial Interface, Power Line Wiring

Page 10

SERIAL INTERFACE

RS-485 interface allows to connect up to 30 devices with one remote master unit.

I

 

 

 

 

A/A'

A'/A

 

N

 

 

 

 

 

11

 

M

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B/B'

B'/B

S

R

 

 

 

 

12

 

 

U

 

 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

M

 

 

 

 

COMMON

 

 

 

 

 

 

R

E

 

 

 

 

 

 

 

13

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 11 - RS-485 WIRING

The cable length must not exceed 1.5 km at 9600 BAUD.

NOTE: The following report describes the signal sense of the voltage appearing across the interconnection cable as defined by EIA for RS-485.

a)The ” A ” terminal of the generator shall be negative with respect to the ” B ” terminal for a binary 1 (MARK or OFF) state.

b)The ” A ” terminal of the generator shall be positive with respect to the ” B ” terminal for a binary 0 (SPACE or ON) state.

D) POWER LINE WIRING

 

 

 

N

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER LINE 100 V to 240 V A.C

 

 

 

 

 

 

 

 

 

 

(50/60Hz)

 

 

 

 

 

 

 

or 24 V AC/DC

 

 

 

 

 

5

 

R (S,T)

 

 

 

 

(S,T)

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 12 POWER LINE WIRING

R

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

1)

Before connecting the instrument to the power

 

 

line, make sure that line voltage corresponds to

 

 

the description on the identification label.

 

 

2)

To avoid electrical shock, connect power line at

 

 

the end of the wiring procedure.

 

 

 

3)

For supply connections use No 16 AWG or larger

 

 

wires rated for at last 75 °C.

 

 

 

4)

Use copper conductors only.

 

 

 

5)

Don’t run input wires together with power cables.

 

6)

For 24 V DC the polarity is a do not care condition.

 

7)

The power supply input is NOT fuse protected.

 

 

Please, provide it externally.

 

 

 

 

 

Power supply

Type

 

Current

 

Voltage

 

 

 

24 V AC/DC

T

 

500 mA

 

250 V

 

 

 

100/240 V AC

T

 

125 mA

 

250 V

 

 

When fuse is damaged, it is advisable to verify

 

 

the power supply circuit, so that it is necessary to

 

 

send back the instrument to your supplier.

 

 

8)

The safety requirements for Permanently Con-

 

 

nected Equipment say:

 

 

 

 

 

 

- a switch or circuit-breaker shall be included in

the building installation;

- It shall be in close proximity to the equipment and within easy reach of the operator;

- it shall be marked as the disconnecting device for the equipment.

7

1604-7-1-AB.p65

7

5/16/00, 10:50 AM

Image 10
Contents Chromalox Contents Model identification IIIMounting Requirements ScrewOutline and CUT OUT Dimensions Outline and CUT-OUT DimensionsConnection Diagrams Measuring Inputs TC InputRTD Input Linear InputRelay Outputs Logic Input Safety noteOUT Linear Output Inductive LoadsLoad Operating Voltage Power Line Wiring Serial InterfaceWhen the Neutral line is present, connect it to terminal Type TC-RTD Preliminary Hardware SettingsInput Open Input CircuitSEr3 = Baude rate for serial link SEr1 = Serial interface protocolOFF SEr4 = Byte format for serial linkP4 = Full scale value P2 = Decimal point positionP3 = Initial scale value P5 = Output 1 functionP8 = analog retransmission full scale value P10 = Alarm 1 operating modeP7 = analog retransmission initial scale value P9 = Output 2 function. nonE = output not usedP14 = Alarm 2 threshold value P12 = Alarm 2 operating modeP15 = Alarm 2 hysteresis value P20 = Secondary control output action P19 = Displayed value of the main power outputP18 = Main control output action P22 = Cooling mediaP28 = Offset adjustment added to the measured value P24 = Alarm 1 actionP26 = Alarm 2 action P29 = Displayable protected parametersP38 = Output safety value P36 = Timeout selectionP34 = Manual function P43 = Set point indication P41 = Control action typeP44 = Operative set point alignment at instrument start up Display Function IndicatorsREM SP2 MAN MAN = SP SP2 SelectionManual Function Direct Access to SET PointLamp Test Smart function Serial LinkHSA1 Alarm 1 hysteresis RSt Manual reset of the alarmsAL1 Alarm 1 threshold AL2 Alarm 2 thresholdRelative Cooling gain Output 3 cycle timeHysteresis for ON/OFF control action Integral timeTOL Time duration of the output power limiter soft start Grd1 Ramp applied to an increasing set point changeOverrange Error MessagesError Messages UnderrangeError List General Informations General SpecificationsInputs Thermocouple Linear Inputs Logic InputControl Actions SET PointsOutputs Alarms OutputSerial Communication Interface MaintenanceStop bit one Address = OFF Appendix a Default ParametersParameter Default Value HSA1, HSA2Para ER0P44 Appendix A.3 Appendix A.4 Chromalox Emerson Electric CO