Chromalox 1604-7 user manual SET Points, Control Actions, Outputs

Page 32

SET POINTS

This instrument allows to use 2 set points: SP and SP2.

The set point selection is possible only by logic input.

Set point transfer:

The transfer between one set point to another (or between two different set point values) may be realized by a step transfer or by a ramp with two different programmable rate of change (ramp up and ramp down).

Slope value: 1 - 100 eng. unit/min or step.

Set points limiter: RLO and RHI parameters, pro- grammable.

CONTROL ACTIONS

Control action: PID + SMART

Type: One (heating or cooling) or two (heating and cooling) control outputs.

Proportional Band (Pb):

Range: - from 1.0 to 100.0 % of the input span for process with one control output.

-from 1.5 to 100.0 % of the input span for process with two control outputs.

When Pb=0, the control action becomes ON/OFF. Hysteresis (for ON/OFF control action):

from 0.1% to 10.0% of the input span.

Integral time (Ti): from 1s to 20 min. or excluded.

Derivative time (Td): from 1 s to 10 min.

If zero value is selected, the derivative action is excluded.

Integral pre-load:

-from 0.0 to 100.0 % for one control output

-from -100.0 (cooling) to +100.0 % (heating) for two control outputs.

SMART: keyboard enabling/disabling

Auto/Manual: selectable by front pushbutton.

Auto/Manual transfer: bumpless method type

Indicator "MAN" : OFF in auto mode and lit in manual mode.

OUTPUTS

Type: This instrument is equipped with 3 independent outputs programmable as follows:

Out 1

Out 2

Out 3

linear (mA)

relay

relay

Heating

AL1

AL2

Heating

Cooling

AL2

Heating

AL1

Cooling

Cooling

AL1

AL2

Cooling

Heating

AL2

Cooling

AL1

Heating

Retransm.

Heating

AL2

Retransm.

AL1

Heating

Retransm.

Cooling

AL2

Retransm.

AL1

Cooling

Retransm.

Heating

Cooling

Retransm.

Cooling

Heating

Retransm.

AL1

AL2

Control output updating time :

-250 ms when a linear input is selected

-500 ms when a TC or RTD input is selected. Action: direct/reverse programmable by front

keyboard.

Output level indication:

The instrument displays separately the output 1 level (heating) and the output 2 level (cooling). Output status indication: the OUT 1 LED will flash with a duty cycle proportional to the output 1 power. Two indicators (OUT 2 and/or OUT 3) are lit when the respective output is in ON condition.

29

1604-7-1-AB.p65

29

5/16/00, 10:50 AM

Image 32
Contents Chromalox Contents Model identification IIIMounting Requirements ScrewOutline and CUT OUT Dimensions Outline and CUT-OUT DimensionsConnection Diagrams Measuring Inputs TC InputRTD Input Linear InputOUT Logic Input Safety noteRelay Outputs Load Operating Voltage Inductive LoadsLinear Output Power Line Wiring Serial InterfaceWhen the Neutral line is present, connect it to terminal Preliminary Hardware Settings InputType TC-RTD Open Input CircuitSEr1 = Serial interface protocol OFFSEr3 = Baude rate for serial link SEr4 = Byte format for serial linkP2 = Decimal point position P3 = Initial scale valueP4 = Full scale value P5 = Output 1 functionP10 = Alarm 1 operating mode P7 = analog retransmission initial scale valueP8 = analog retransmission full scale value P9 = Output 2 function. nonE = output not usedP15 = Alarm 2 hysteresis value P12 = Alarm 2 operating modeP14 = Alarm 2 threshold value P19 = Displayed value of the main power output P18 = Main control output actionP20 = Secondary control output action P22 = Cooling mediaP24 = Alarm 1 action P26 = Alarm 2 actionP28 = Offset adjustment added to the measured value P29 = Displayable protected parametersP34 = Manual function P36 = Timeout selectionP38 = Output safety value P44 = Operative set point alignment at instrument start up P41 = Control action typeP43 = Set point indication REM SP2 MAN IndicatorsDisplay Function MAN = SP SP2 SelectionLamp Test Direct Access to SET PointManual Function Smart function Serial LinkRSt Manual reset of the alarms AL1 Alarm 1 thresholdHSA1 Alarm 1 hysteresis AL2 Alarm 2 thresholdOutput 3 cycle time Hysteresis for ON/OFF control actionRelative Cooling gain Integral timeTOL Time duration of the output power limiter soft start Grd1 Ramp applied to an increasing set point changeError Messages Error MessagesOverrange UnderrangeError List Inputs Thermocouple General SpecificationsGeneral Informations Linear Inputs Logic InputOutputs SET PointsControl Actions Alarms OutputStop bit one Address MaintenanceSerial Communication Interface Appendix a Default Parameters Parameter Default Value= OFF HSA1, HSA2Para ER0P44 Appendix A.3 Appendix A.4 Chromalox Emerson Electric CO