Chromalox 1604-7 user manual P12 = Alarm 2 operating mode, P14 = Alarm 2 threshold value

Page 16

P12 = Alarm 2 operating mode

Available only when P11 is equal to "AL2.P", "AL2.b" or "AL2.d".

H.A. = High alarm (outside for band alarm) with automatic reset (latched).

L.A. = Low alarm (inside for band alarm) with automatic reset (latched).

H.L. = High alarm (outside band) with manual reset (latched).

L.L.= low alarm (inside band) with manual reset (latched).

P13 = Programmability of the alarm 2 threshold and hysteresis values

Available only when P11 is equal to "AL2.P", "AL2.b" or "AL2.d".

OPrt = Alarm 2 threshold and hysteresis are programmable in the operating mode.

COnF = Alarm 2 threshold and hysteresis are programmable in configuration mode.

P14 = Alarm 2 threshold value

Available only when P11 is equal to "AL2.P", "AL2.b" or "AL2.d" and P13 is equal to "COnF". Range: For process alarm - within the range

limits.

For band alarm - from 0 to 500 units. For deviation alarm - from -500 to 500 units.

P15 = Alarm 2 hysteresis value

Available only when P11 is equal to "AL2.P", "AL2.b" or "AL2.d" and P13 is equal to "COnF". Range: from 0.1% to 10.0 % of the range selected

with P3 and P4 parameters, or 1 LSD.

P16 = Threshold of the “Soft Start” function. Threshold value in eng. units to initiate the "Soft start" function (output power limiting) at start up. Range : within the readout span.

NOTE: This threshold value will not be taken into account when tOL = InF.

P17 = Safety lock

0 = No parameter protection. The device is always in unlock condition and all parameters can be modified.

1 = The device is always in lock condition and no one of the parameters (exception made for set points [SP, SP2] and manual reset of the alarms) can be modified (for SMART status see P30 parameter).

From 2 to 4999 = This combination number is a secret value to be used, in run time (see nnn parameter) to put the device in lock/unlock condition.

For SP, SP2 and manual reset of the alarms, the lock/unlock condition has no effect (for SMART status see P30).

From 5000 to 9999 = This combination number is a secret value to be used, in run time (see

nnnparameter) to put the device in lock/ unlock condition.

For SP, SP2, manual reset of the alarm, AL1, AL2, the lock/unlock condition has no effect (for SMART status see P30).

NOTE:when safety lock is selected, the secret value can not be displayed again and the display will show 0, 1, SFt.A (when P17 is encompassed between 2 and 4999) or SFt.b (when P17 is encompassed between 5000 and 9999)

13

1604-7-1-AB.p65

13

5/16/00, 10:50 AM

Image 16
Contents Chromalox Contents Model identification IIIMounting Requirements ScrewOutline and CUT OUT Dimensions Outline and CUT-OUT DimensionsConnection Diagrams Measuring Inputs TC InputRTD Input Linear InputRelay Outputs Logic Input Safety noteOUT Linear Output Inductive LoadsLoad Operating Voltage Power Line Wiring Serial InterfaceWhen the Neutral line is present, connect it to terminal Preliminary Hardware Settings InputType TC-RTD Open Input CircuitSEr1 = Serial interface protocol OFFSEr3 = Baude rate for serial link SEr4 = Byte format for serial linkP2 = Decimal point position P3 = Initial scale valueP4 = Full scale value P5 = Output 1 functionP10 = Alarm 1 operating mode P7 = analog retransmission initial scale valueP8 = analog retransmission full scale value P9 = Output 2 function. nonE = output not usedP14 = Alarm 2 threshold value P12 = Alarm 2 operating modeP15 = Alarm 2 hysteresis value P19 = Displayed value of the main power output P18 = Main control output actionP20 = Secondary control output action P22 = Cooling mediaP24 = Alarm 1 action P26 = Alarm 2 actionP28 = Offset adjustment added to the measured value P29 = Displayable protected parametersP38 = Output safety value P36 = Timeout selectionP34 = Manual function P43 = Set point indication P41 = Control action typeP44 = Operative set point alignment at instrument start up Display Function IndicatorsREM SP2 MAN MAN = SP SP2 SelectionManual Function Direct Access to SET PointLamp Test Smart function Serial LinkRSt Manual reset of the alarms AL1 Alarm 1 thresholdHSA1 Alarm 1 hysteresis AL2 Alarm 2 thresholdOutput 3 cycle time Hysteresis for ON/OFF control actionRelative Cooling gain Integral timeTOL Time duration of the output power limiter soft start Grd1 Ramp applied to an increasing set point changeError Messages Error MessagesOverrange UnderrangeError List General Informations General SpecificationsInputs Thermocouple Linear Inputs Logic InputControl Actions SET PointsOutputs Alarms OutputSerial Communication Interface MaintenanceStop bit one Address Appendix a Default Parameters Parameter Default Value= OFF HSA1, HSA2Para ER0P44 Appendix A.3 Appendix A.4 Chromalox Emerson Electric CO