Chromalox 1604-7 P2 = Decimal point position, P3 = Initial scale value, P4 = Full scale value

Page 14
----.= No decimal figure.
---.-= One decimal figure. --.--= Two decimal figures. -.---= Three decimal figures.

21

= TC type

J

range

-150

/

+1830

°F

22

= TC type

K

range

-150

/

+2500

°F

23

= TC type

T

range

-330

/

+750

°F

24

= TC type

N

range

-150

/

+2550

°F

25

= TC type

R

range

0

/

+3200

°F

26

= TC type

S

range

0

/

+3200

°F

27= RTD type Pt 100 range-199.9 / +400.0 °F

28= RTD type Pt 100 range -330 / +1470 °F NOTE: selecting P1 = 0, 2, 4, 6, 10 or 27, the instrument set automatically P39 = P40 = FLtr. For all the remaining ranges it will set P39 = P40 = nOFL.

If a different selection is desired, P39 and P40 may be modified, after executed P1 configuration.

P2 = Decimal point position

This parameter is available only when a linear input is selected (P1 = 12, 13, 14, 15, 16, 17, 18 or 19).

P3 = Initial scale value

For linear inputs it is programmable from -1999 to 4000.

For TC and RTD input, it is programmable within the input range.

When this parameter is modified, rL parameter will be re-aligned to it.

P4 = Full scale value

For linear inputs it is programmable from -1999 to 4000.

For TC and RTD input it is programmable within

the input range.

When this parameter is modified, rH parameter will be re-aligned to it.

The initial and full scale values determine the input span which is used by the PID algorithm, the SMART and the alarm functions.

NOTE: the minimum input span (S = P4 - P3), in absolute value, should be set as follows:

For linear inputs, S > 100 units.

For TC input with °C readout, S > 300 °C. For TC input with °F readout, S > 550 °F. For RTD input with °C readout, S > 100 °C. For RTD input with °F readout, S > 200 °F.

P5 = Output 1 function

rEv

=

Out 1 is used as control output with

 

 

reverse action

dir

=

Out 1 is used as control output with direct

 

 

action

Pv.rt =

Out 1 is used as analog retransmission of

 

 

the measured value (process variable)

SP.rt = Out 1 is used as analog retransmission of the operative set point.

REVERSE ACTION

DIRECT ACTION

Input

Input

 

 

 

 

t

t

Output

 

 

 

Output

 

 

 

 

 

t

t

 

 

 

 

P6 = Output 1 type.

0-20 = output type 0 - 20 mA. 4-20 = output type 4 - 20 mA.

11

1604-7-1-AB.p65

11

5/16/00, 10:50 AM

Image 14
Contents Chromalox Contents Model identification IIIMounting Requirements ScrewOutline and CUT OUT Dimensions Outline and CUT-OUT DimensionsConnection Diagrams Measuring Inputs TC InputRTD Input Linear InputOUT Logic Input Safety noteRelay Outputs Load Operating Voltage Inductive LoadsLinear Output Power Line Wiring Serial InterfaceWhen the Neutral line is present, connect it to terminal Type TC-RTD Preliminary Hardware SettingsInput Open Input CircuitSEr3 = Baude rate for serial link SEr1 = Serial interface protocolOFF SEr4 = Byte format for serial linkP4 = Full scale value P2 = Decimal point positionP3 = Initial scale value P5 = Output 1 functionP8 = analog retransmission full scale value P10 = Alarm 1 operating modeP7 = analog retransmission initial scale value P9 = Output 2 function. nonE = output not usedP15 = Alarm 2 hysteresis value P12 = Alarm 2 operating modeP14 = Alarm 2 threshold value P20 = Secondary control output action P19 = Displayed value of the main power outputP18 = Main control output action P22 = Cooling mediaP28 = Offset adjustment added to the measured value P24 = Alarm 1 actionP26 = Alarm 2 action P29 = Displayable protected parametersP34 = Manual function P36 = Timeout selectionP38 = Output safety value P44 = Operative set point alignment at instrument start up P41 = Control action typeP43 = Set point indication REM SP2 MAN IndicatorsDisplay Function MAN = SP SP2 SelectionLamp Test Direct Access to SET PointManual Function Smart function Serial LinkHSA1 Alarm 1 hysteresis RSt Manual reset of the alarmsAL1 Alarm 1 threshold AL2 Alarm 2 thresholdRelative Cooling gain Output 3 cycle timeHysteresis for ON/OFF control action Integral timeTOL Time duration of the output power limiter soft start Grd1 Ramp applied to an increasing set point changeOverrange Error MessagesError Messages UnderrangeError List Inputs Thermocouple General SpecificationsGeneral Informations Linear Inputs Logic InputOutputs SET PointsControl Actions Alarms OutputStop bit one Address MaintenanceSerial Communication Interface = OFF Appendix a Default ParametersParameter Default Value HSA1, HSA2Para ER0P44 Appendix A.3 Appendix A.4 Chromalox Emerson Electric CO