21 | = TC type | J | range | / | +1830 | °F | |
22 | = TC type | K | range | / | +2500 | °F | |
23 | = TC type | T | range | / | +750 | °F | |
24 | = TC type | N | range | / | +2550 | °F | |
25 | = TC type | R | range | 0 | / | +3200 | °F |
26 | = TC type | S | range | 0 | / | +3200 | °F |
27= RTD type Pt 100
28= RTD type Pt 100 range
If a different selection is desired, P39 and P40 may be modified, after executed P1 configuration.
P2 = Decimal point position
This parameter is available only when a linear input is selected (P1 = 12, 13, 14, 15, 16, 17, 18 or 19).
P3 = Initial scale value
For linear inputs it is programmable from
For TC and RTD input, it is programmable within the input range.
When this parameter is modified, rL parameter will be
P4 = Full scale value
For linear inputs it is programmable from
For TC and RTD input it is programmable within
the input range.
When this parameter is modified, rH parameter will be
The initial and full scale values determine the input span which is used by the PID algorithm, the SMART and the alarm functions.
NOTE: the minimum input span (S = P4 - P3), in absolute value, should be set as follows:
For linear inputs, S > 100 units.
For TC input with °C readout, S > 300 °C. For TC input with °F readout, S > 550 °F. For RTD input with °C readout, S > 100 °C. For RTD input with °F readout, S > 200 °F.
P5 = Output 1 function
rEv | = | Out 1 is used as control output with |
|
| reverse action |
dir | = | Out 1 is used as control output with direct |
|
| action |
Pv.rt = | Out 1 is used as analog retransmission of | |
|
| the measured value (process variable) |
SP.rt = Out 1 is used as analog retransmission of the operative set point.
REVERSE ACTION | DIRECT ACTION | ||||
Input | Input | ||||
|
|
|
| t | t |
Output |
|
|
| Output | |
| |||||
|
|
|
| t | t |
|
|
|
|
P6 = Output 1 type.