P24 = Alarm 1 action
Available only when P9 = "AL1.P", "AL1.d" or "AL1.b".
dir = direct action (relay energized in alarm condi- tion)
rEV = reverse action (relay
P25 = alarm 1
OFF =
NOTE: If the alarm is programmed as band or deviation alarm, this function masks the alarm condition after a set point change or at the instrument
P26 = Alarm 2 action
Available only when P11 = "AL2.P", "AL2.d" or "AL2.b".
dir = direct action (relay energized in alarm condition)
rEV = reverse action (relay
P27 = Alarm 2
OFF =
NOTE: for more details to
P28 = OFFSET adjustment added to the measured value
This parameter allows to set a constant OFFSET throughout the readout range.
It is skipped for linear inputs
-For readout ranges with decimal figure, P28 is programmable from
-For readout ranges without decimal figure, P28 is programmable from
Readout Real curve
P28 | Adjusted |
| |
| curve |
Input
P29 = Displayable protected parameters
This parameter is skipped when P17 = 0.
OFF = Protected parameters cannot be displayed. On = Protected parameter can be displayed.
P30 = SMART function
This parameter is skipped when none of the outputs is programmed as control output.
0 = SMART function disabled.
1 = SMART function is NOT protected by safety lock.
2 = SMART function is under safety lock protection.