PRELIMINARY HARDWARE SETTINGS

1)Remove the instrument from its case.

2)It is necessary to set J106 according to the desired input type as shown in the following figure.

INPUT

 

 

J106

 

 

 

 

 

 

 

 

TYPE

1-2

3-4

5-6

7-8

9-10

TC-RTD

open

close

open

open

open

60 mV

open

close

open

open

open

 

 

 

 

 

 

5 V

close

open

close

open

open

10 V

open

open

close

open

open

20 mA

open

open

open

close

close

OPEN INPUT CIRCUIT

This instrument is able to identify the open circuit for TC and RTD inputs.

The open input circuit condition for RTD input is shown by an "overrange" indication.

For TC input, it is possible to select overrange indication (standard) or underrange indication set- ting the CH101 and SH101 according to the follow- ing table:

Overrange (STD) CH101

= close SH101

= open

Underrange

CH101

= open SH101

= close

Both pads are located on the soldering side of the CPU card

NOTE : the not used jumper can be positioned on pin 7-9

2 4 6 8 10

V101 J106

1 3 5 7 9

Fig. 13

CH101 SH101

Fig. 14

9

1604-7-1-AB.p65

9

5/16/00, 10:50 AM

Image 12
Contents Chromalox Contents Model identification IIIMounting Requirements ScrewOutline and CUT OUT Dimensions Outline and CUT-OUT DimensionsConnection Diagrams Measuring Inputs TC InputRTD Input Linear InputLogic Input Safety note Relay OutputsOUT Inductive Loads Linear OutputLoad Operating Voltage Power Line Wiring Serial InterfaceWhen the Neutral line is present, connect it to terminal Preliminary Hardware Settings InputType TC-RTD Open Input CircuitSEr1 = Serial interface protocol OFFSEr3 = Baude rate for serial link SEr4 = Byte format for serial linkP2 = Decimal point position P3 = Initial scale valueP4 = Full scale value P5 = Output 1 functionP10 = Alarm 1 operating mode P7 = analog retransmission initial scale valueP8 = analog retransmission full scale value P9 = Output 2 function. nonE = output not usedP12 = Alarm 2 operating mode P14 = Alarm 2 threshold valueP15 = Alarm 2 hysteresis value P19 = Displayed value of the main power output P18 = Main control output actionP20 = Secondary control output action P22 = Cooling mediaP24 = Alarm 1 action P26 = Alarm 2 actionP28 = Offset adjustment added to the measured value P29 = Displayable protected parametersP36 = Timeout selection P38 = Output safety valueP34 = Manual function P41 = Control action type P43 = Set point indicationP44 = Operative set point alignment at instrument start up Indicators Display FunctionREM SP2 MAN MAN = SP SP2 SelectionDirect Access to SET Point Manual FunctionLamp Test Smart function Serial LinkRSt Manual reset of the alarms AL1 Alarm 1 thresholdHSA1 Alarm 1 hysteresis AL2 Alarm 2 thresholdOutput 3 cycle time Hysteresis for ON/OFF control actionRelative Cooling gain Integral timeTOL Time duration of the output power limiter soft start Grd1 Ramp applied to an increasing set point changeError Messages Error MessagesOverrange UnderrangeError List General Specifications General InformationsInputs Thermocouple Linear Inputs Logic InputSET Points Control ActionsOutputs Alarms OutputMaintenance Serial Communication InterfaceStop bit one Address Appendix a Default Parameters Parameter Default Value= OFF HSA1, HSA2Para ER0P44 Appendix A.3 Appendix A.4 Chromalox Emerson Electric CO