RTD INPUT

RTD

8 9 10

RTD

8 9 10

LINEAR INPUT

 

 

10

+

mA,

 

 

mV

 

_

or

9

V

 

 

 

Shield

10

+

mA

 

 

 

_

mV

9

or

 

 

 

V

Fig. 5 RTD INPUT WIRING

NOTE:

1)Don’t run input wires together with power cables.

2)Pay attention to the line resistance; a high line resistance may cause measurement errors.

3)When shielded cable is used, it should be grounded at one side only to avoid ground loop currents.

4)The resistance of the 3 wires must be the same.

G

Fig. 6 mA, mV AND V INPUTS WIRING

NOTE:

1)Don’t run input wires together with power cables.

2)Pay attention to the line resistance; a high line resistance may cause measurement errors.

3)When shielded cable is used, it should be grounded at one side only to avoid ground loop currents.

4)The input impedance is equal to: < 5 W for 20 mA input

>1 MW for 60 mV input

>200 kW for 5 V input

>400 kW for 10 V input

4

1604-7-1-AB.p65

4

5/16/00, 10:50 AM

Image 7
Contents Chromalox Contents III Model identificationScrew Mounting RequirementsOutline and CUT-OUT Dimensions Outline and CUT OUT DimensionsMeasuring Inputs TC Input Connection DiagramsLinear Input RTD InputRelay Outputs Logic Input Safety noteOUT Linear Output Inductive LoadsLoad Operating Voltage Serial Interface Power Line WiringWhen the Neutral line is present, connect it to terminal Open Input Circuit Preliminary Hardware SettingsInput Type TC-RTDSEr4 = Byte format for serial link SEr1 = Serial interface protocolOFF SEr3 = Baude rate for serial linkP5 = Output 1 function P2 = Decimal point positionP3 = Initial scale value P4 = Full scale valueP9 = Output 2 function. nonE = output not used P10 = Alarm 1 operating modeP7 = analog retransmission initial scale value P8 = analog retransmission full scale valueP14 = Alarm 2 threshold value P12 = Alarm 2 operating modeP15 = Alarm 2 hysteresis value P22 = Cooling media P19 = Displayed value of the main power outputP18 = Main control output action P20 = Secondary control output actionP29 = Displayable protected parameters P24 = Alarm 1 actionP26 = Alarm 2 action P28 = Offset adjustment added to the measured valueP38 = Output safety value P36 = Timeout selectionP34 = Manual function P43 = Set point indication P41 = Control action typeP44 = Operative set point alignment at instrument start up Display Function IndicatorsREM SP2 MAN SP SP2 Selection MAN =Manual Function Direct Access to SET PointLamp Test Serial Link Smart functionAL2 Alarm 2 threshold RSt Manual reset of the alarmsAL1 Alarm 1 threshold HSA1 Alarm 1 hysteresisIntegral time Output 3 cycle timeHysteresis for ON/OFF control action Relative Cooling gainGrd1 Ramp applied to an increasing set point change TOL Time duration of the output power limiter soft startUnderrange Error MessagesError Messages OverrangeError List General Informations General SpecificationsInputs Thermocouple Logic Input Linear InputsControl Actions SET PointsOutputs Output AlarmsSerial Communication Interface MaintenanceStop bit one Address HSA1, HSA2 Appendix a Default ParametersParameter Default Value = OFFER0 ParaP44 Appendix A.3 Appendix A.4 Emerson Electric CO Chromalox