Chromalox 1604-7 user manual Logic Input Safety note, Relay Outputs

Page 8
op. set point
SP
SP2

B)LOGIC INPUT Safety note:

1) Do not run logic input wiring together with power cables.

2) Use an external dry contact capable of switching 0.5 mA, 5 V DC.

3) The instrument needs 100 ms to recognize a contact status variation.

4) The logic inputs are NOT isolated by the measuring input

C) RELAY OUTPUTS

1

OUT 2

3

OUT 3

2

NO - OUT 2

NO - OUT 3

C - OUT 2 and 3

SP / SP2

14

15

Fig. 7 - LOGIC INPUT WIRING

This logic input allows to select the operative set point.

logic input

open close

Fig. 8 RELAY OUTPUTS WIRING

The contact rating of the OUT 2, 3 is 2A/250V AC on resistive load.

The number of operations is 1 x 105 at specified rating.

NOTES 1) To avoid electrical shock, connect power line at the end of the wiring procedure.

2)For power connections use No 16 AWG or larger wires rated for at last 75 °C.

3)Use copper conductors only.

4)Don’t run input wires together with power cables.

The relay contacts are protected by varistor against inductive load with inductive component up to 0.5 A.

The following recommendations avoid serious problems which may occur, when using relay output for driving inductive loads.

5

1604-7-1-AB.p65

5

5/16/00, 10:50 AM

Image 8
Contents Chromalox Contents Model identification IIIMounting Requirements ScrewOutline and CUT OUT Dimensions Outline and CUT-OUT DimensionsConnection Diagrams Measuring Inputs TC InputRTD Input Linear InputOUT Logic Input Safety noteRelay Outputs Load Operating Voltage Inductive LoadsLinear Output Power Line Wiring Serial InterfaceWhen the Neutral line is present, connect it to terminal Preliminary Hardware Settings InputType TC-RTD Open Input CircuitSEr1 = Serial interface protocol OFFSEr3 = Baude rate for serial link SEr4 = Byte format for serial linkP2 = Decimal point position P3 = Initial scale valueP4 = Full scale value P5 = Output 1 functionP10 = Alarm 1 operating mode P7 = analog retransmission initial scale valueP8 = analog retransmission full scale value P9 = Output 2 function. nonE = output not usedP15 = Alarm 2 hysteresis value P12 = Alarm 2 operating modeP14 = Alarm 2 threshold value P19 = Displayed value of the main power output P18 = Main control output actionP20 = Secondary control output action P22 = Cooling mediaP24 = Alarm 1 action P26 = Alarm 2 actionP28 = Offset adjustment added to the measured value P29 = Displayable protected parametersP34 = Manual function P36 = Timeout selectionP38 = Output safety value P44 = Operative set point alignment at instrument start up P41 = Control action typeP43 = Set point indication REM SP2 MAN IndicatorsDisplay Function MAN = SP SP2 SelectionLamp Test Direct Access to SET PointManual Function Smart function Serial LinkRSt Manual reset of the alarms AL1 Alarm 1 thresholdHSA1 Alarm 1 hysteresis AL2 Alarm 2 thresholdOutput 3 cycle time Hysteresis for ON/OFF control actionRelative Cooling gain Integral timeTOL Time duration of the output power limiter soft start Grd1 Ramp applied to an increasing set point changeError Messages Error MessagesOverrange UnderrangeError List Inputs Thermocouple General SpecificationsGeneral Informations Linear Inputs Logic InputOutputs SET PointsControl Actions Alarms OutputStop bit one Address MaintenanceSerial Communication Interface Appendix a Default Parameters Parameter Default Value= OFF HSA1, HSA2Para ER0P44 Appendix A.3 Appendix A.4 Chromalox Emerson Electric CO