Chromalox 1604-7 user manual P41 = Control action type, P43 = Set point indication

Page 20

NOTE: when the instrument detects an out of range condition, it assignes the P38 value to the PID output but P18 and P20 parameter are still active.

P39 = Digital filter on the displayed value It is possible to apply to the displayed value a digital filter of the first order with a time constant equal to :

-4 s for TC and RTD inputs

-2 s for linear inputs nOFL. = no filter

FLtr = filter enabled

P40 = Digital filter on the retransmitted value This parameter is available only if P5 = PV.rt.

It is possible to apply to the retransmitted value a digital filter of the first order with a time constant equal to :

-4 s for TC and RTD inputs

-2 s for linear inputs nOFL. = no filter

FLtr = filter enabled

P41 = Control action type

This parameter is skipped when none of the outputs is programmed as control output.

Pid. = The process is controlled by PID action. Pi. = The process is controlled by PI action.

negative value decreases the low limit of the anti- reset-wind up (under set point).

P43 = Set point indication

Fn.SP = during operative mode, when the instrument performs a ramp, it will show the final set point value.

OP.SP =during operative mode, when the instrument performs a ramp, it will show the operative set point.

P44 = Operative set point alignment at instrument start up

0 = At start up, the operative set point will be aligned to SP or SP2 according to the digital input status.

1 = At start up, the operative set point will be aligned to the measured value, the selected set point value will be reached by the programmed ramp (see Grd1 and Grd2 operative parameters).

NOTE: if the instrument detects an out of range or an error condition on the measured value it will ever operate as described for P44 = 0.

P42 = Extension of the anti-reset-wind up Range: from -30 to +30 % of the proportional band.

NOTE: a positive value increases the high limit of the anti-reset-wind up (over set point) while a

The configuration procedure is terminated and the display returns to show "COnF".

17

1604-7-1-AB.p65

17

5/16/00, 10:50 AM

Image 20
Contents Chromalox Contents Model identification IIIMounting Requirements ScrewOutline and CUT OUT Dimensions Outline and CUT-OUT DimensionsConnection Diagrams Measuring Inputs TC InputRTD Input Linear InputOUT Logic Input Safety noteRelay Outputs Load Operating Voltage Inductive LoadsLinear Output Power Line Wiring Serial InterfaceWhen the Neutral line is present, connect it to terminal Preliminary Hardware Settings InputType TC-RTD Open Input CircuitSEr1 = Serial interface protocol OFFSEr3 = Baude rate for serial link SEr4 = Byte format for serial linkP2 = Decimal point position P3 = Initial scale valueP4 = Full scale value P5 = Output 1 functionP10 = Alarm 1 operating mode P7 = analog retransmission initial scale valueP8 = analog retransmission full scale value P9 = Output 2 function. nonE = output not usedP15 = Alarm 2 hysteresis value P12 = Alarm 2 operating modeP14 = Alarm 2 threshold value P19 = Displayed value of the main power output P18 = Main control output actionP20 = Secondary control output action P22 = Cooling mediaP24 = Alarm 1 action P26 = Alarm 2 actionP28 = Offset adjustment added to the measured value P29 = Displayable protected parametersP34 = Manual function P36 = Timeout selectionP38 = Output safety value P44 = Operative set point alignment at instrument start up P41 = Control action typeP43 = Set point indication REM SP2 MAN IndicatorsDisplay Function MAN = SP SP2 SelectionLamp Test Direct Access to SET PointManual Function Smart function Serial LinkRSt Manual reset of the alarms AL1 Alarm 1 thresholdHSA1 Alarm 1 hysteresis AL2 Alarm 2 thresholdOutput 3 cycle time Hysteresis for ON/OFF control actionRelative Cooling gain Integral timeTOL Time duration of the output power limiter soft start Grd1 Ramp applied to an increasing set point changeError Messages Error MessagesOverrange UnderrangeError List Inputs Thermocouple General SpecificationsGeneral Informations Linear Inputs Logic InputOutputs SET PointsControl Actions Alarms OutputStop bit one Address MaintenanceSerial Communication Interface Appendix a Default Parameters Parameter Default Value= OFF HSA1, HSA2Para ER0P44 Appendix A.3 Appendix A.4 Chromalox Emerson Electric CO