Chromalox 1604-7 user manual Display Function, Indicators, REM SP2 MAN

Page 21

OPERATIVE MODE

1)Remove the instrument from its case.

2)Set the internal dip switch V101 in closed condi- tion

3)Re-insert the instrument.

4)Switch on the instrument.

DISPLAY FUNCTION

The upper display shows the measured value while the lower display shows the programmed set point value (we define the above condition as “normal display mode”).

NOTE : When the rate of change (Grd1, Grd2) is utilized, the displayed set point value may be different from the operating set point.

It is possible to change the information on the lower display as follows:

-Push FUNC pushbutton for more than 3 seconds but less than 10 seconds.

The lower display will show " r. " followed by

the power value of the OUT programmed as "rEV" control output (from 0.0 to 100.0%*).

-Push FUNC pushbutton again. The lower display will show "d." followed by the power value of the

OUT programmed as "dir" control output (from 0.0 to 100.0%*).

*The graphic symbol " . " means 100%.

-Push FUNC pushbutton again. The display will return in "Normal Display Mode".

NOTE : The two power outputs are displayed only if the relative function has been previously configured.

When no pushbutton is pressed during the time out (see P36), the display will automatically return in "Normal Display Mode".

In order to keep the desired information continuously on the lower display, depress s or

tpush-button to remove the timeout.

When return in "Normal Display Mode" is desired, push FUNC push-button again.

INDICATORS

°C Lit when the process variable is shown in Celsius degrees.

°F Lit when the process variable is shown in Fahrenheit degrees.

SMRT Flashing when the first part of the SMART algorithm is active.

Lit when the second part of the SMART algorithm is active.

OUT1 It will flash with a duty cycle proportional to the linear output value.

OUT2 Lit when OUT 2 is ON or alarm 1 is in the alarm state.

OUT3 Lit when OUT 3 is ON or alarm 2 is in the alarm state

Other functions are shown by decimal points:

REM

SP2

MAN

REM = Flashing, when the instrument is controlled via serial link.

SP2 = Flashing at slow rate when SP2 is used. Flashing at fast rate when a set point from serial link is used.

MAN= Flashing at slow rate, when the instrument is in MANUAL mode.

18

1604-7-1-AB.p65

18

5/16/00, 10:50 AM

Image 21
Contents Chromalox Contents III Model identificationScrew Mounting RequirementsOutline and CUT-OUT Dimensions Outline and CUT OUT DimensionsMeasuring Inputs TC Input Connection DiagramsLinear Input RTD InputLogic Input Safety note Relay OutputsOUT Inductive Loads Linear OutputLoad Operating Voltage Serial Interface Power Line WiringWhen the Neutral line is present, connect it to terminal Input Preliminary Hardware SettingsType TC-RTD Open Input CircuitOFF SEr1 = Serial interface protocolSEr3 = Baude rate for serial link SEr4 = Byte format for serial linkP3 = Initial scale value P2 = Decimal point positionP4 = Full scale value P5 = Output 1 functionP7 = analog retransmission initial scale value P10 = Alarm 1 operating modeP8 = analog retransmission full scale value P9 = Output 2 function. nonE = output not usedP12 = Alarm 2 operating mode P14 = Alarm 2 threshold valueP15 = Alarm 2 hysteresis value P18 = Main control output action P19 = Displayed value of the main power outputP20 = Secondary control output action P22 = Cooling mediaP26 = Alarm 2 action P24 = Alarm 1 actionP28 = Offset adjustment added to the measured value P29 = Displayable protected parametersP36 = Timeout selection P38 = Output safety valueP34 = Manual function P41 = Control action type P43 = Set point indicationP44 = Operative set point alignment at instrument start up Indicators Display FunctionREM SP2 MAN SP SP2 Selection MAN =Direct Access to SET Point Manual FunctionLamp Test Serial Link Smart functionAL1 Alarm 1 threshold RSt Manual reset of the alarmsHSA1 Alarm 1 hysteresis AL2 Alarm 2 thresholdHysteresis for ON/OFF control action Output 3 cycle timeRelative Cooling gain Integral timeGrd1 Ramp applied to an increasing set point change TOL Time duration of the output power limiter soft startError Messages Error MessagesOverrange UnderrangeError List General Specifications General InformationsInputs Thermocouple Logic Input Linear InputsSET Points Control ActionsOutputs Output AlarmsMaintenance Serial Communication InterfaceStop bit one Address Parameter Default Value Appendix a Default Parameters= OFF HSA1, HSA2ER0 ParaP44 Appendix A.3 Appendix A.4 Emerson Electric CO Chromalox